Benchmark 6000 Boiler Installation, Operation & Maintenance Manual
CHAPTER 5 – MODE OF OPERATION
OMM-0086_0D
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
75
of
210
GF-133
Ph.: 800-526-0288
03/20/14
The following two options are available for using a combination system; one that uses only the
ACS, and one that requires the optional ACS Relay Box:
•
OPTION 1
- This option is selected when the ACS controls a boiler plant containing up to
eight combination boilers that are Domestic Hot Water Priority (DHW PRIORITY) boilers,
along with building heat (BLDG HEAT) boilers, and
one
hydronic isolation valve in the main
header between the BLDG HEAT boilers and the DHW PRIORITY boilers.
•
OPTION 2
– When this option is selected, the ACS Relay Panel must be used in
conjunction with the ACS. For this option, the ACS controls a boiler plant containing up to
eight combination boilers that are divided up into Building Priority (BLDG PRIORITY) boilers
and Domestic Hot Water Priority (DHW PRIORITY) boilers, along with building heat (BLDG
HEAT) boilers, and using
two
hydronic isolation valves in the main header, one between the
BLDG HEAT and BLDG PRIORITY boilers, and the other between the BLDG PRIORITY
and the DHW PRIORITY boilers.
In Option 2, when the space-heating load is such that when all the space-heating boilers are at
the 100% valve position, the ACS will then ask the ACS Relay Box for the domestic boilers to
become space-heating boilers. Provided the domestic hot water load is satisfied, the combo (hot
water) boilers will then become space-heating boilers. If the domestic hot water load is not
satisfied, the combo boiler(s) remain on the domestic hot water load. If the combo boilers switch
over to space heating, but there is a call for domestic hot water, the ACS Relay Box switches the
combo units back to the domestic load. The ACS in combination with the ACS Relay Box will ask
the BLDG PRIORITY boilers to help with domestic hot water heating if the DHW PRIORITY
boilers are not able to satisfy the domestic hot water demand.
When the combo units are satisfying the domestic load, they are in the constant setpoint mode of
operation. When the combo units switch over to space heating, their mode of operation changes
to follow the ACS command. For more information concerning the operation of the ACS, consult
the ACS Operations Guide, GF-131. For more information on the ACS Relay Box, see section
2.14 in the same manual.
5.7.1 Combination Control System Field Wiring
Wiring for this system is between the ACS, the ACS Relay Box, and the terminals in the I/O Box.
Wire the units using a shielded twisted pair of 18 to 22 AWG wire. When wiring multiple units,
each unit’s wiring must conform to the above.
5.7.2 Combination Control System Setup and Startup
Setup for the Combination Mode requires entries to be made in the Configuration Menu for boiler
mode, remote signal type and setpoint. The setpoint is adjustable from 40°F to 190°F.
Enter the following settings in the Configuration Menu:
Menu Option
Setting
Boiler Mode
Combination
Remote Signal
Network
Internal Setpt
40°F to 190°F
Refer to section 3.3 for instructions on changing menu options.
While it is possible to change other temperature-related functions for combination mode, these
functions are preset to their factory default values. These default settings work well in most