Benchmark 6000 Boiler Installation, Operation & Maintenance Manual
CHAPTER 2 – INSTALLATION
OMM-0086_0D
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
29
of
210
GF-133
Ph.: 800-526-0288
03/20/14
DO NOT make any connections to the I/O Box terminals labeled “NOT
USED”. Attempting to do so may cause equipment damage.
Figure 2-13: I/O Box Terminal Strips
2.10.1 OUTDOOR AIR IN Terminal
An OUTDOOR AIR IN terminal is used for connecting an outdoor temperature sensor (AERCO
P/N GM-123525) as required primarily for the Indoor/Outdoor reset mode of operation. It can
also be used with another mode if it is desired to use the outdoor sensor enable/disable feature.
This feature allows the boiler to be enabled or disabled based on the outdoor air temperature.
The factory default for the outdoor sensor is DISABLED. To enable the sensor and/or select an
enable/disable outdoor temperature, see the Configuration menu in Chapter 3.
The outdoor sensor may be wired up to 200 feet from the boiler. It is connected to the
OUTDOOR AIR IN and AIR SENSOR COMMON terminals of the I/O Box (see Figure 2-13).
Wire the sensor using a twisted shielded pair wire between 18 and 22 AWG. There is no polarity
to observe when terminating these wires. The shield is to be connected only to the terminals
labeled SHIELD in the I/O Box. The sensor end of the shield must be left free and ungrounded.
When mounting the sensor, it must be located on the North side of the building where an
average outside air temperature is expected. The sensor must be shielded from direct sunlight
as well as impingement by the elements. If a shield cover is used, it must allow for free air
circulation.
CAUTION