Benchmark 6000 Boiler Installation, Operation & Maintenance Manual
CHAPTER 4 – INITIAL START-UP
OMM-0086_0D
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
65
of
210
GF-133
Ph.: 800-526-0288
03/20/14
Natural Gas Combustion Calibration (Cont.)
18. Press the
MENU
key on the front panel of the C-MORE and access the
Setup
menu. Enter
password 6817 and then press the
ENTER
key.
19. Press the
MENU
key on the front panel of the C-MORE until
Combustion Cal Menu
appears on the display.
20.
Press the ▲ arrow key until
SET Valve Position
appears on the display.
21. Press the
CHANGE
key.
SET Valve Position
will begin to flash.
22.
Press the ▲ arrow key until the
SET Valve Position
reads
80%
. Press the
ENTER
key.
23.
Next, press the down (▼) arrow key until
CAL Voltage 70%
is displayed.
24. Press the
CHANGE
key and observe that
CAL Voltage 70%
is flashing.
25. The oxygen level at the 70% valve position should be as shown below. Also, ensure that
the nitrogen oxide (NOx) and carbon monoxide (CO) readings do not exceed the following
values:
Combustion Calibration Readings
Valve Position
Oxygen (O
2
) %
Nitrogen Oxide (NOx)
Carbon Monoxide (CO)
70%
6.0% - 6.5%
<20 ppm
<100 ppm
26.
If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼
arrow keys. This will adjust the output voltage to the blower motor as indicated on the
display. Pressing the ▲ arrow key increases the oxygen level and pressing the down ▼
arrow key decreases the oxygen level.
27. Once the oxygen level is within the specified range at 70%, press the
ENTER
key to store
the selected blower output voltage for the 80% valve position. Record all readings on the
Combustion Calibration Sheets provided.