Benchmark 6000 Boiler Installation, Operation & Maintenance Manual
CHAPTER 3 – OPERATION
Page
52
of
210
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0086_0D
03/20/14
Ph.: 800-526-0288
GF-133
4.
Next, the blower proof switch on the Air/Fuel Valve (Figure 3-5) closes. The display will
show
Purging
and indicate the elapsed time of the purge cycle in seconds.
Figure 3-5: Blower Proof Switch
NOTE
A Function Timing Chart for the BMK6000 Proved Pilot Control
System is provided in Figure 3-7, below.
5.
Upon completion of the purge cycle, the Control Box initiates an ignition cycle and the
following events occur:
a) The Air/Fuel Valve rotates to the low-fire (Ignition Position) position and closes the
ignition switch. The Dial on the Air/Fuel Valve will read between
45
and
50
(Figure 3-6)
to indicate that the valve is in the low-fire position.
b) Power is supplied to the Spark Igniter.
c) Power is supplied to the Pilot Gas Solenoid.
d) The Optical Pilot Flame Sensor proves the Pilot Flame and the red LED stops
blinking and changes to steady ON.
e) Ignition relay 1 (R1) closes allowing the main Burner ignition sequence to start.
BLOCKED INLET
SWITCH
BLOWER PROOF
SWITCH
AIR/FUEL VALVE
ASSEMBLY
MANUAL SHUT-
OFF VALVE
BLOWER