Flame Fault Tests
1. Set the
ON/OFF
switch to the
OFF
position.
2. Place the unit in the Manual Mode and set the valve position between 25% and 30%.
3. Close the manual gas shutoff valve located between the Safety Shut-Off Valve (SSOV)
and the Air/Fuel Valve (see Figure 6-3).
4.
Set the
ON/OFF
switch to the
ON
position to start the unit.
5.
The unit should purge and light the Pilot flame and then shut down after reaching the main
Burner Ignition cycle and display
FLAME LOSS DURING IGN.
6.
Open the valve previously closed in step 3 and press the
CLEAR
button.
7. Restart the unit and allow it to prove flame.
8. Once flame is proven, close the manual gas valve located between the SSOV and the
Air/Fuel Valve (Figure 6-3).
9. The unit should shut down and Lockout. A flashing
FLAME LOSS DURING RUN
should
appear in the display.
10. Open the valve previously closed in step 8.
11. Press the
CLEAR
button. The unit should restart and fire.
Figure 6-3: Bare Boiler – Partial View
6.8 AIR FLOW FAULT TESTS
These tests check the operation of the Blower Proof Switch and Blocked Inlet Switch shown in
Figure 6-4.
AIR FILTERS
MANUAL GAS
SHUT-OFF VALVE
GAS TRAIN
AIR/FUEL VALVE
BLOWER
Y-DUCT