6.4 PERIODIC INSPECTION & SERVICING
Inspection & servicing should only be
carried out by a ‘Competent Person’ who has sufficient knowledge to
check the whole system. This would normally be a qualified electrical contractor or fire alarm specialist.
Inspection & servicing visits are normally conducted on a quarterly basis unless such factors as a dirty
environment warrant servicing on a more regular basis. The maximum period between inspections must not
exceed six months.
Recommendations of BS5839-1 for periodic service visits include:
•
Every device on the system should be tested annually. The testing of each device can be split between
periodic visits but with a minimum of one detector or call point tested on each circuit, per visit.
•
On each visit the ‘Competent Person’ should check the record of false alarms. Any persistent occurrence
should be investigated and corrective action taken as appropriate.
•
Battery and connections should be examined and load tested to check serviceable condition and that they
are not likely to fail before the next service visit.
•
All other devices and control & indicating equipment should be checked for correct operation and any faults
should be recorded and rectified.
•
Details of the service visit must be recorded in the log book
EVERY FOUR YEARS
Renew the sealed lead acid batteries and record the fact in the log book
www.acornfiresecurity.com
www.acornfiresecurity.com
Summary of Contents for Quick Zone XL
Page 5: ...5 1 2 CABINET DETAILS www acornfiresecurity com www acornfiresecurity com...
Page 8: ...8 1 4 MAIN PCB TERMINALS www acornfiresecurity com www acornfiresecurity com...
Page 15: ...15 2 3 GENERAL TWIN WIRE SYSTEM SCHEMATIC www acornfiresecurity com www acornfiresecurity com...
Page 66: ...66 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com...
Page 67: ...USER NOTES www acornfiresecurity com www acornfiresecurity com...
Page 68: ...www acornfiresecurity com www acornfiresecurity com...