1 ABOUT THIS PANEL
1.1 PRODUCT OVERVIEW
The QuickZone XL panel is available from 4 to 12 Conventional and/or Twin Wire (sav-wire) zones.
For the fire alarm engineer, the QuickZone XL has been designed to minimise labour costs by providing ample
room for tasks such as wiring and changing batteries. Activation is via key switch or access code, which means
you should always be able to work on the panel and the one man walk tests will help reduce the cost of
maintaining the fire alarm system.
Simplicity is one of the most important aspects when considering the end user of a fire alarm panel. The colour
coded buttons and the 3 step silence functionality gives non-technical people the confidence to correctly
manage their fire alarm system.
All inputs and outputs are fully programmable and there are options to have delays to the outputs. The
programming features of the QuickZone XL also include 3 different modes to help reduce false alarms. Local
fire authorities are demanding this type of functionality to reduce unwanted callouts from alarm receiving centres
As standard, all QuickZone XL panels provide two monitored sounder circuits, Fire & Fault VFCO relays, Fire &
Fault switched negative outputs, class change and an alert input.
A fully functional repeater panel is available via a plug in comms PCB.
QuickZone XL panels support a large range of conventional detectors including, Apollo, Hochiki & Nittan.
The panels are supplied with a 3.0 amp internal power supply module. This module complies with the
requirements of EN54-4 : 1988 and provides temperature compensated battery management charging.
QuickZone XL panels are approved to European standards EN54-2 & 4, Fire Detection and Alarm Systems
–
Control & Indicating Equipment.
Quiesecent and alarm current details for standby battery calculations
Model
Standby Current
Alarm Current
QZXL-4
90mA
133mA
Add per Twin Wire circuit
N/A
9mA
QZXL-ZEC 4 Zone ext card std
43mA
47mA
QZXL-HAZEC 4 zone ext card, high spec
49mA
87mA
TPCA05 comms card
5.2mA
N/A
www.acornfiresecurity.com
www.acornfiresecurity.com
Summary of Contents for Quick Zone XL
Page 5: ...5 1 2 CABINET DETAILS www acornfiresecurity com www acornfiresecurity com...
Page 8: ...8 1 4 MAIN PCB TERMINALS www acornfiresecurity com www acornfiresecurity com...
Page 15: ...15 2 3 GENERAL TWIN WIRE SYSTEM SCHEMATIC www acornfiresecurity com www acornfiresecurity com...
Page 66: ...66 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com...
Page 67: ...USER NOTES www acornfiresecurity com www acornfiresecurity com...
Page 68: ...www acornfiresecurity com www acornfiresecurity com...