Panel Wide Settings
There are 6 general, panel wide, settings available.
Enter the above code and press the ENTER button. The 6
programmable options are represented by fire zone LEDs 1 - 6.
Use button 1 to move to option required as per table;
Fire LED
Programming Option
1
Change / remove keypad access code
2
Set number of repeater panels on system
3
Set output delay time (1 - 10 minutes)
4
Turn off battery monitoring
5
Set up internal PCB configuration (add
extension zone card or repeater comms
PCB)
6
Change repeater comms monitoring
1. Change / Remove Keypad Access Code
The keypad can be used to activate the panel controls instead of using the key switch. The default code is 1-2-
3-4; however, this can be changed. It is also possible to disable the use of a code entry to enable controls,
forcing the use of the key switch only.
Enter the above code and press the ENTER button. The Zone Fault/Disabled/Test LEDs will start to rapidly
pulse in sequence to show the currently set code. The sequence will be repeated twice after which time the
panel will automatically drop out of the set keypad entry mode.
Whilst the current code sequence is being repeated start to enter the new code. Enter the new code slowly and
deliberately, one number at a time. The corresponding Zone Fault/Disabled/Test LED will rapidly pulse to
confirm each entry.
Note: Enable Controls codes must always start with a 1 or 2.
When finished entering the new four digit code, press the ENTER button. The panel will then confirm the new
code with rapidly pulsing LEDs in sequence, after which time the panel will automatically drop out of the set
keypad entry mode.
Changing the keypad code to 1 - 1 - 1 - 1 will disable the use of a keypad to enable controls.
Press button 1 to move to next option or press and hold button
1 for 3 seconds to exit programming mode 2-1-2-3. (The panel
will confirm the new access code one more time before exiting
the programming mode).
www.acornfiresecurity.com
www.acornfiresecurity.com
Summary of Contents for Quick Zone XL
Page 5: ...5 1 2 CABINET DETAILS www acornfiresecurity com www acornfiresecurity com...
Page 8: ...8 1 4 MAIN PCB TERMINALS www acornfiresecurity com www acornfiresecurity com...
Page 15: ...15 2 3 GENERAL TWIN WIRE SYSTEM SCHEMATIC www acornfiresecurity com www acornfiresecurity com...
Page 66: ...66 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com...
Page 67: ...USER NOTES www acornfiresecurity com www acornfiresecurity com...
Page 68: ...www acornfiresecurity com www acornfiresecurity com...