22
4.3 LEVEL 3 ENGINEERING OPTIONS
A series of programmable engineering options are available. These
programming modes are initiated by entering a four digit code using buttons 1
- 4 on the keypad followed by the ENTER button.
To access Level 3 options, first set switch 3 on the 3 way DIL switch located on the main PCB to the ‘ON’
position. Then activate the controls by turning the key switch or by entering the four digit code (see Activate
Controls in the OPERATING section).
Once the controls are active, t
he ‘Access Level’ indicator will pulse rapidly to signify that Level 3 access is
active.
Programming throughout the panel is carried out in a sequence where the fire LEDs indicate the options to set
and the fault / disabled / test LEDs indicate the status of these settings.
Generally button 1 is used to scroll the indications (button 3 can also be used to scroll backwards).
Pressing and holding button 1 for 3 seconds at any time will exit the programming mode completely.
N.B.
The panel will automatically save settings & drop out of programming modes if left idle for more than
approximately 30 seconds.
It is possible to review the settings within a programming mode without changing them. Steady Fire LEDs
indicate review mode. To edit a setting first use button 1 to select the required option, pressing ENTER enables
editing of the option. Flashing fire LEDs indicates edit mode and button 2 is used to change the setting.
Pressing ENTER again will exit ‘edit’ mode back to ‘review’ mode.
Some programming modes are denoted with (EN54!). Where this symbol appears EN54 compliance may be
affected by this setting.
www.acornfiresecurity.com
www.acornfiresecurity.com
Summary of Contents for Quick Zone XL
Page 5: ...5 1 2 CABINET DETAILS www acornfiresecurity com www acornfiresecurity com...
Page 8: ...8 1 4 MAIN PCB TERMINALS www acornfiresecurity com www acornfiresecurity com...
Page 15: ...15 2 3 GENERAL TWIN WIRE SYSTEM SCHEMATIC www acornfiresecurity com www acornfiresecurity com...
Page 66: ...66 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com...
Page 67: ...USER NOTES www acornfiresecurity com www acornfiresecurity com...
Page 68: ...www acornfiresecurity com www acornfiresecurity com...