Output Programmability & Miscellaneous
All of the relays & outputs on the control panel’s main circuit board (TPC-A01) have default functions, i.e.
operate on fire or fault. The function for each of these outputs, however, can be changed. The outputs can also
be programmed to have different responses for selected zones.
Before any programming can be applied to the main circuit board outputs, they must first be made
programmable using this mode.
Mode 4-1-4-2 also has 2 other miscellaneous functions, these are:
Set Fault Latching
- This sets the latching of all faults on the panel. A useful tool for capturing any random or
intermittent faults.
Invert Fault Output
- The switched -ve fault output on the main circuit board usually appears when a fault is
present. This can be inverted so that the output is constant and disappears when a fault occurs, for fail safe
operation.
To set either of the two miscellaneous options above or to make outputs programmable, enter the above code
and press ENTER.
The fire zone 1 LED will now pulse to indicate the setting of attribute 1 (fault latching).
Use button 1 to scroll to the attribute that requires setting,
indicated by a pulsing fire LED 1 - 6 as per table below.
The setting of the attribute is indicated by the amber, fault /
disabled / test LED, ON or OFF.
Fire LED
(pulsing)
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
Attribute
Fault
latching
Invert Fault
Output
Fault Relay
Programmable
Fault Output
Programmable
Fire Relay
Programmable
Fire Output
Programmable
With the required fire LED pulsing, use button 2 to switch the
attribute ON or OFF (amber, fault / disabled / test LED, ON or
OFF).
When finished, press and hold Button 1 for 3 seconds to save setting and exit programming mode
Enter the next programming code or disable the controls and return DIL switch 3 to ‘OFF’.
www.acornfiresecurity.com
www.acornfiresecurity.com
Summary of Contents for Quick Zone XL
Page 5: ...5 1 2 CABINET DETAILS www acornfiresecurity com www acornfiresecurity com...
Page 8: ...8 1 4 MAIN PCB TERMINALS www acornfiresecurity com www acornfiresecurity com...
Page 15: ...15 2 3 GENERAL TWIN WIRE SYSTEM SCHEMATIC www acornfiresecurity com www acornfiresecurity com...
Page 66: ...66 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com...
Page 67: ...USER NOTES www acornfiresecurity com www acornfiresecurity com...
Page 68: ...www acornfiresecurity com www acornfiresecurity com...