48
5 OPERATING
5.1 PANEL CONTROLS & INDICATIONS
Activate Controls
In normal standby mode the keypad controls are inactive to protect from unauthorised operation. Controls can
be activated by using the ‘Activate Controls’ key switch or by entering a four digit code using the keypad.
The use of a code entry to activate the controls is enabled by default but can be disabled in the Level 3
engineering functions.
To activate the controls using the key switch; turn the key clockwise to the ‘On’ position. The ‘Access Level’
indicator LED will light and all buttons on the keypad will now be operational. To deactivate the controls, turn the
key back to the ‘Off’ position and the ‘Access Level’ indicator LED will extinguish.
If the key switch is in the ‘On’ position the keypad will remain active.
NOTE
: It is not possible to remove the key in the ‘On’ position.
To activate the controls using the keypad; first push button 1 or button 2 to initialise the code entry mode. The
‘Access Level’ indicator will pulse rapidly. After 30 seconds, if the code has not been entered, the panel will
return to standby mode.
With the ‘Access Level’ indicator pulsing, enter the four digit code using buttons 1 - 4. The factory default code
is 1-2-3-4 but can be changed in the engineering functions. After entering the four
digit code press the ‘ENTER’
button. The ‘Access Level’ indicator LED will change to steady and all buttons on the keypad will now be
operational.
If the wrong code has been entered the ‘Access Level’ indicator will continue to pulse. Enter the code again and
press the ‘ENTER’ button. If after 30 seconds the correct code has still not been entered the panel will return to
standby and button 1 or 2 will need to be pushed again to initialise code entry mode.
After activation by code entry, controls will automatically deactivate again after 2 minutes and the panel will
return to standby mode.
The test lamps and mute buzzer functions are operational without the need to activate controls.
www.acornfiresecurity.com
www.acornfiresecurity.com
Summary of Contents for Quick Zone XL
Page 5: ...5 1 2 CABINET DETAILS www acornfiresecurity com www acornfiresecurity com...
Page 8: ...8 1 4 MAIN PCB TERMINALS www acornfiresecurity com www acornfiresecurity com...
Page 15: ...15 2 3 GENERAL TWIN WIRE SYSTEM SCHEMATIC www acornfiresecurity com www acornfiresecurity com...
Page 66: ...66 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com...
Page 67: ...USER NOTES www acornfiresecurity com www acornfiresecurity com...
Page 68: ...www acornfiresecurity com www acornfiresecurity com...