37
Input Function Settings
The QuickZone XL has two inputs located on the main circuit board, Class Change (CC) and Alert (PUL).
Switching a negative voltage into these inputs will cause the alarm sounders to operate. The Class Change
input (CC) will cause the alarms to sound continuously and the Alert input (PUL) will cause the alarms to pulse.
Either or both of these inputs can be
programmed to have a different
function.
The available functions are:
•
Class Change (continuous
sounder operation).
•
Alert (pulsing sounder
operation).
•
Evacuate (a latching input
which activates all the alarms
and shows a general fire indication on the panel).
•
Silence (for remote silence alarms control).
•
Reset (for remote reset control).
•
Fire Zone 12 (a non-latching input which indicates zone 12 fire LED).
•
Fault Zone 12 (a non-latching input which indicates zone 12 fault LED).
To change the default function of the inputs, enter the above code and press ENTER. The zone 1 fire LED will
illuminate. This indicates setting the function of the CC input.
Use button 1 to move to zone 2 fire LED for setting the
function of the PUL input and then back to zone 1 again.
The current setting for the input will be indicated by the
amber, fault / disabled / test LEDs as per table below.
With the required fire LED lit, as per above, press the ENTER
button to enter ‘editing mode’. The fire zone 1 LED will now
pulse to indicate function 1 (Class Change).
Now use button 1 to
move the pulsing fire
LED to the required
setting as per the table
below, then use button 2
to select the function.
The amber, fault /
disabled / test LED will
move to indicate the
new current setting.
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
Class
Change
Alert
Evacuate
Remote
Silence
Alarms
Remote
Reset
Fire Zone 12
Fault Zone
12
Press the ENTER button again to return to input selection.
When finished, press and hold Button 1 for 3 seconds to save setting and exit programming mode.
Enter the next programming code or disable the cont
rols and return DIL switch 3 to ‘OFF’.
www.acornfiresecurity.com
www.acornfiresecurity.com
Summary of Contents for Quick Zone XL
Page 5: ...5 1 2 CABINET DETAILS www acornfiresecurity com www acornfiresecurity com...
Page 8: ...8 1 4 MAIN PCB TERMINALS www acornfiresecurity com www acornfiresecurity com...
Page 15: ...15 2 3 GENERAL TWIN WIRE SYSTEM SCHEMATIC www acornfiresecurity com www acornfiresecurity com...
Page 66: ...66 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com...
Page 67: ...USER NOTES www acornfiresecurity com www acornfiresecurity com...
Page 68: ...www acornfiresecurity com www acornfiresecurity com...