Setting this option to
Off
will disable forwarding of packets by both routers until arbitration
completes and only one router goes active. e default is
Off
.
Status SNVT Update Time
: e twin monitoring application has a status SNVT type 93. If bound
the status SNVT is propagated either on a timer or when it is updated by the monitoring
application or both or neither. e Status SNVT update time determines the maximum time
between propagations. If the update time is non zero, every update time ms a status SNVT is
scheduled for propagation. It is propagated even if the status has not been updated. If the update
time is zero then no propagation is scheduled on a timed interval. For a more detailed description
of the Status SNVT see Section 2.5.5.
Status SNVT Send on Update
: is option schedules the status SNVT for propagation whenever
the SNVT is updated or the status changes. is is event driven and not time driven. For a more
detailed description of the status SNVT see Section 2.5.5.
Twin IP Address
: is field displays/sets the redundant twin’s IP address
Twin IP Por
t: is field displays/sets the redundant twin’s IP port
709 Domain
: ese fields display the common domain address used for both the IP and LON
709.1 stacks.
Twin IP side Subnet/Node
: is field displays the subnet/node address of the twin’s IP side 709.1
stack.
Twin LON CN side Subnet/Node
: is field displays the subnet/node address of the twin’s LON
component network side 709.1 stack.
Twin Mode ON/OFF
: ese radio buttons turn twin mode on or off.
Trigger Twin App Service Pin
: is button propagates a service pin message from the twin mode
monitoring application. is enables remote commissioning of the twin mode application.
Clear Twin LON CN Config
: is button clears the component network configuration about its
twin from this device’s memory.
Sync Data From Twin
: is button manually requests a sync packet from its twin.
Sync Data To Twin
: is button manually sends a sync packet to its twin.
Submit Changes
: is button updates the configuration memory of the device and refreshes the
web page to reflect any changes.
2.12. Twin Mode Status Page
e
Twin Mode Status Page
displays operational state and statistics information about the
Redundant Twin Mode
operation. Twin mode is an optional enhancement and is not activated in
a standard router. If your device does not support
Redundant Twin Mode
contact Adept to find
out how it might be activated. Following is a brief description of each item listed on the page.
-53-
Summary of Contents for GRouter3
Page 1: ...GRouter3 Single Port 709 1 852 Router User Guide 3 03 2007 02 10...
Page 13: ...Fig 1 8 Unicast Fig 1 9 Mulitcast 13...
Page 22: ...Fig 1 14 Power port detail e le most pin of the rightmost connector is chassis ground 22...
Page 56: ...Fig 2 23 Contacts Page 56...
Page 60: ...Fig 3 2 Initial LonMaker Drawing Fig 3 3 Router Channel Setup 60...
Page 66: ...Fig 3 9 New Virtual Functional Device Dialog Fig 3 10 Functional Blocks NV Shapes Dialog 66...