SETTING ECONOMY AIR OPERATION VIA CONTROL INTERFACE
2. Temp difference to enable cycle:
(Configurable “Gfd2” )
This setting is the difference required between the Room Air Temp. (
T
Room
) and the Outside Air Temp. (
T
Outside Air
).
If (
T
Room
- T
Outside Air
)
> Temp difference to enable cycle
, the economy air will operate.
Settings: Min = -2.0
O
C, Max = 9.9
O
C, Default = 2.0
O
C
3. Min Outside Air temp.:
(Configurable in “Gfd2”)
This setting activates the economy damper. If the
T
Outside Air
<
Min Outside Air Temp
, the economy cycle will stop
and the damper will remain open with minimum opening value set by
Min Outside pos
.
Settings: Min = 0.0
O
C, Max = 25.0
O
C, Default = 14.0
O
C
Enabled: NO
Economy Cycle Gfd2
Enabled: YES
Temperature Diff: 2.0
˚
C
Outside Air Min Limit
Temperature: No
Economy Cycle Gfd2
SCREEN WHEN ECONOMY CYCLE
IS DISABLED
SCREEN WHEN ECONOMY CYCLE
IS ENABLED
4. Max Outside Air temp.:
(Configurable in “Gfd3”)
This setting activates the economy damper. If the
T
Outside Air
>
Max Outside Air Temp
, the economy cycle will stop
and the damper will remain open with maximum opening value set by
Min Outside pos
.
Settings: Min = 0.0
O
C, Max = 25.0
O
C, Default = 16.0
O
C
Outside Air Max Limit
Temperature: Yes 16.0
˚
C
Economy Cycle Gfd3
5. Damper Scaling:
(Configurable in “Gfc19”)
Damper opening calibration may be configured Service Menu “Gfc19”.
NOTE:
The settable damper output is 20% - 100% as any setting below 2V is considered closed.
Settings: Default Output Start = 20%, Default Output End = 100%
NOTE:
When one of Settings 1 - 4 is satisfied for 180 seconds (configurable), economy cycle may begin operation.
For the system to exit economy cycle operation, conditions of settings 1 - 4 should be false for a period of 180
seconds.
Damper Scaling
Command Start: 0%
Command End: 100%
Output Start: 0%
Output End: 100%
Economy Cycle Gf19