60
Installation & Commissioning Guide PKY470-700 Tri-Capacity Package with CM100 Control
Doc. No.0525-032
Ver. 9 180921
AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
50
100
150
200
250
300
350
400
450
500
%
Spd. W
%
Spd. W
%
Spd. W
%
Spd. W
%
Spd. W
%
Spd. W
%
Spd. W
%
Spd. W
%
Spd. W
%
Spd. W
2500
53.7 777 57.5 965 61.2 1151 65.0 1330 68.3 925 71.5 1745 74.3 1956 78.0 2173 81.9 2426 85.0 2660
2600
55.5 837 59.2 1035 62.9 1221 66.6 1423 70.0 1632 72.9 1851 76.1 2071 80.0 2285 83.5 2555 88.0 2823
2700
57.5 920 61.0 1111 64.8 1305 68.3 1523 71.5 1744 74.5 1972 78.0 2175 81.7 2418 84.8 2659
2800
59.6 1011 63.1 1199 66.7 1407 70.0 1615 73.0 1852 76.2 2076 80.0 2285 83.2 2537 88.0 2834
2900
61.6 1095 65.0 1277 68.5 1507 71.5 1724 74.5 1962 78.1 2176 81.8 2425 85.0 2680
3000
63.5 1173 66.8 1372 70.2 1596 73.1 1834 76.6 2083 80.3 2303 83.5 2558 88.2 2846
3100
65.5 1263 68.9 1487 71.9 1716 74.9 1962 78.9 2207 82.1 2442 85.6 2686
3200
67.6 1377
70.8 1593
73.7 1842 77.1 2080 81.0 2341 84.0 2584 88.9 2822
3300
69.6 1439 72.5 1715 75.6 1958 79.5 2206 82.9 2480 86.6 2727
3400
71.5 1601 74.4 1845 78.2 2097 81.6 2349 84.8 2628
3500
73.3 1721 77.0 1993 80.5 2230 83.3 2479 88.2 2748
3600
75.8 1878 79.5 2122 82.5 2383 85.9 2640
MOTOR / BLOWER LIMIT
3700
78.6 2018 81.6 2262 84.5 2538
3800
81.9 2237 83.7 2419 90.0 2670
3900
82.9 2287 87.8 2563
EC INDOOR FAN COMMISSIONING
PKY620T- 6Q2
FAN PERFORMANCE DATA
INDOOR UNIT FAN CURVE
IMPORTANT NOTE:
Fan Performance Data & Fan Curve shown is at dry coil and with
no air filters installed. Consider ext. static pressure drop specific to
your design requirements.
AIRFLOW (l/s)
Nominal Airflow = 3200 l/s
EXTERNAL
ST
ATIC
PRESSURE (Pa)
APPLICATION RANGE
2500
3200
3100
3900
2800
3500
2600
3300
2900
3600
2700
3400
3000
3700
500
250
400
150
300
50
0
450
200
350
100
0
50
100
150
200
250
300
350
400
450
500
2500
2600
2700
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
70.8% Speed
90% Speed
85% Speed
80% Speed
75% Speed
70% Speed
60% Speed
55% Speed
65% Speed
MOTOR / BLOWER LIMIT
Thermoregulation Gfc4
Supply Fan
Minimum Temp.
5.0
o
C
Maximum Temp.
50.0
o
C
Minimum speed:
53.7%
Medium speed:
70.8%
Maximum speed:
90.0%
Supply Fan Temp.
Set Fan Speed
*
Service
Service Settings
Thermoregulation
Thermoregulation Gfc4
NOTES:
% Speed
= Indoor Fan Speed Control Setting, in percent
(Value is set on the Control Interface via Service Menu
*
).
W
= Indoor Fan Power, Watts
- Data in the box indicates Factory Default Setting.