ALARM MATRIX
ALARMS - DESCRIPTIONS - CONDITIONS
Description
Type Alarm Condition
Reset Condition
Discharge Temperature 1 /
High Pressure Comp 1 Fault
Alarm
Temperature out of Range
Normal Operating
Temperature
Pd > 4500kPa
Pd < 3506kPa
Discharge Temperature 2 /
High Pressure Comp 2 Fault
Alarm
Temperature out of Range
Normal Operating
Temperature
Pd > 4500kPa
Pd < 3506kPa
Compressor 1 LP Fault
Ps < 165kPa
Ps > 330kPa
Compressor 2 LP Fault
Ps < 165kPa
Ps > 330kPa
Outdoor Coil Temp1 Fault
Warning Temperature out of Range
Normal Operating
Temperature
Outdoor Coil Temp2 Fault
Warning Temperature out of Range
Normal Operating
Temperature
Room Air Temperature
Sensor Fault
Warning Temperature out of Range
Normal Operating
Temperature
Outside Air Temperature
Sensor Fault
Warning Temperature out of Range
Normal Operating
Temperature
Indoor Coil Sensor Fault
Warning Temperature out of Range
Normal Operating
Temperature
Filter Alarm
Alarm
Air Filter Timer Timed-Out
Clean / Replace Filter
and Reset Timer
Anti-Freeze Protection
Warning Indoor Coil
Temperature Too Low
Normal Operating
Temperature