AIRFLOW
(l/s)
EXTERNAL STATIC PRESSURE (Pa)
50
100
150
200
250
300
350
400
450
500
%
Spd. W
%
Spd. W
%
Spd. W
%
Spd. W
%
Spd. W
%
Spd. W
%
Spd. W
%
Spd. W
%
Spd. W
%
Spd. W
2800
59.6 1011 63.1 1199 66.7 1407 70.0 1615 73.0 1852 76.2 2076 80.0 2285 83.2 2537 88.0 2834
2900
61.6 1095 65.0 1277 68.5 1507 71.5 1724 74.5 1962 78.1 2176 81.8 2425 85.0 2680
3000
63.5 1173 66.8 1372 70.2 1596 73.1 1834 76.6 2083 80.3 2303 83.5 2558 88.2 2846
3100
65.5 1263 68.9 1487 71.9 1716 74.9 1962 78.9 2207 82.1 2442 85.6 2686
3200
67.6 1377 70.8 1593 73.7 1842 77.1 2080 81.0 2341 84.0 2584 88.9 2822
3300
69.6 1439 72.5 1715 75.6 1958 79.5 2206 82.9 2480 86.6 2727
3400
71.5 1601 74.4 1845 78.2 2097 81.6 2349 84.8 2628
3500
73.3 1721 77.0 1993 80.5 2230 83.3 2479 88.2 2748
3600
75.8 1878
79.5 2122
82.5 2383 85.9 2640
3700
78.6 2018 81.6 2262 84.5 2538
MOTOR / BLOWER LIMIT
3800
81.9 2237 83.7 2419 90.0 2670
3900
82.9 2287 87.8 2563
4000
85.0 2460
EC INDOOR FAN COMMISSIONING
PKY700T- 6Q2
FAN PERFORMANCE DATA
INDOOR UNIT FAN CURVE
IMPORTANT NOTE:
Fan Performance Data & Fan Curve shown is at dry coil and with
no air filters installed. Consider ext. static pressure drop specific to
your design requirements.
AIRFLOW (l/s)
Nominal Airflow = 3600 l/s
EXTERNAL
ST
ATIC
PRESSURE (Pa)
APPLICATION RANGE
2800
3400
4000
3100
3700
2900
3500
3200
3800
3000
3600
3300
3900
500
250
400
150
300
50
0
450
200
350
100
0
50
100
150
200
250
300
350
400
450
500
2800
2900
3000
3100
3200
3300
3400
3500
3600
3700
3800
3900
4000
79.5% Speed
90% Speed
85% Speed
80% Speed
75% Speed
70% Speed
65% Speed
60% Speed
MOTOR / BLOWER LIMIT
Thermoregulation Gfc4
Supply Fan
Minimum Temp.
5.0
o
C
Maximum Temp.
50.0
o
C
Minimum speed:
59.6%
Medium speed:
79.5%
Maximum speed:
90.0%
Supply Fan Temp.
Set Fan Speed
*
Service
Service Settings
Thermoregulation
Thermoregulation Gfc4
NOTES:
% Speed
= Indoor Fan Speed Control Setting, in percent
(Value is set on the Control Interface via Service Menu
*
).
W
= Indoor Fan Power, Watts
- Data in the box indicates Factory Default Setting.