ELECTRICAL
MAXIMUM CABLE LENGTHS
CABLE RUN
DESCRIPTION
SUGGESTED
MAXIMUM CABLE LENGTH
1 to 2
Outdoor CM100 to Optional ActronAir CP05 / CP10 Control Interface (Dual Control)
50m / 200m - See Note D
1 to 3
Outdoor CM100 to Return Air Sensor (NTC Sensor Input Cable Size 0.5mm
2
/ 1.0mm
2
)
50m / 100m
1 to 4
Outdoor CM100 to ActronAir CP05 (Remotely re-located Factory Supplied Control Interface)
50m / 200m - See Note D
1 to 5
Outdoor CM100 to Third Party Control
Refer to Third Party Control Supplier
NOTES:
A. Diagram shown above is a general presentation only. Refer to individual unit wiring diagram for complete wiring connection details.
B. Long cable runs beside supply mains or TV antenna cables should be avoided where possible.
C. Return Air Sensor needs to be installed by the installer specific to site requirements.
D. Suggested Maximum Cable Length: 50m when using Flat Telephone Cable / 200m when using 6 Core (3Pair)Twisted Pair Shielded Data Cable.
For compliance with EMC requirements, connect screen wire to Terminal 22 on the Outdoor Panel.
*
Room Air Sensor is factory supplied with 6m cable as standard. Sensor may need adjustment for longer cable lengths.
**
Do not extend the factory supplied data cable when re-locating the Control Interface. Replace the cable with a single length
of either of the data cables specified above.
1
PACKAGE UNIT
(OPTIONAL DUAL CONTROL)
CONTROL INTERFACE
ActronAir
®
CP05 / CP10
(Purchased Seperately)
CP05 - or - CP10
- or -
2
4
3
3
2
Esc
Prg
(OPTIONAL REMOTE RE-LOCATION)
ActronAir
®
CP05
CONTROL INTERFACE
**
(Factory Supplied)
ActronAir
®
2060-036
ROOM AIR SENSOR
*
(Factory Supplied)
ActronAir
®
LM-RS
ROOM AIR SENSOR
(Optional)
3RD PARTY CONTROL
INPUT TERMINALS
6
6 Core (3 Pair) Twisted Pair
7/0.20 (AWG24) Shielded Data Cable
(
Installer to Provide
)
or
6 Core Flat
7/0.12 (AWG28) Telephone Cable
(
Installer to Provide
)
NTC Sensor Cable
(Factory Supplied)
6 Core (3 Pair) Twisted Pair
7/0.20 (AWG24)
Shielded Data Cable
(
Installer to Provide
)
or
6 Core Flat
7/0.12 (AWG28)
Telephone Cable
(