EC INDOOR FAN COMMISSIONING
EC FAN COMMISSIONING VIA CP05 / CP10 CONTROL INTERFACE
INDOOR FAN SPEED SETTING PROCEDURE VIA CONTROL INTERFACE
1.
Refer to the Fan Performance Data or the Fan Curve specific to your air conditioner.
2.
Determine the % Fan Speed which matches your Airflow and External Static Pressure requirements using either the
Fan Performance Data or the Fan Curve.
3. Example -
Unit Model PKY470T-6Q2: Airflow of 2400 l/s with External Static Press of 100 Pa
will require 71.9% Fan Speed.
4. Use this determined Fan Speed % to set the medium speed via the control interface, following the menu navigation:
G.
Service
Gfc.
Service Settings
Gfc.
Thermoregulation
Gfc4.
Thermoregulation (Supply Fan Settings).
Thermoregulation Gfc4
Supply Fan
Minimum Temp.
5.0
o
C
Maximum Temp.
50.0
o
C
Minimum speed:
49.0%
Medium speed:
71.9%
Maximum speed:
90.0%
Supply Fan Temp.
% Medium Fan Speed
% Maximum Fan Speed
NOTES
:
• Minimun and Maximum fan speeds are factory default settings.
• Medium fan speed is the nominal operating fan speed which can be adjusted between the min and max speed.
Commissioning of EC Fan should be carried out by
qualified technician
only.
Make sure that all instructions are followed accordingly.
Ensure that connecting duct work and air filters are installed accordingly.