ELECTRICAL
DUAL CONTROL INTERFACE CONNECTION PROCEDURES
1. Thread the Data Cable through the unit
and into the electrical panel.
•
Ensure to secure the cable firmly to the unit, using
cable ties and the provided clamp.
2. Connect the Data Cable to the secondary
Control Interface allocated terminal blocks.
• Refer control cable connections to wiring diagram
provided to units with dual control.
3. Mount the secondary Control Interface to a remote and connect the other end of the control cable into
secondary control interface RJ12 socket.
• Refer mounting Cut-out & Mounting holes details to Control Interface Insert Part No. 0525-035.
Secondary Control Interface
Remote Location
Secondary
Control Interface
(
Installer to Supply
)
Screws
(2-off)
Panel
Mounting Cut-out
(127mm x 69mm)
Panel
Mounting Holes
(2 x
ø
2.5mm)
Cover
Control Interface
RJ12
Connector
Connect Data Cable to
Terminal Blocks # 19,20,21 &22
Refer dual control wiring connections
to CP05 - CP10 Control Interface Insert
Doc. No. 0525-035
Secure the control cable firmly
using the cable ties and clamp
provided in the panels.
6 Core (3 Pair) Twisted Pair
7/0.20 (AWG24) Shielded Data Cable
(
Installer to Provide
)
or
6 Core Flat 7/0.12 (AWG28)
Telephone Cable
(
Installer to Provide
)