COMPRESSORS AND INDOOR FANS MODES OF OPERATION
3.2.2
Enable the Multi Input assigned to the Compressors via S.Configuration screen
Gfc8
:
NOTES:
◦
For "W- 3 Phase Sequence Relay Option", Multi Input 2 (U12) is already used for 24VAC supply. Hence,
enable Multi Input 1 (U11) instead.
Display Progression:
G. Service
F. Alarm History
Main Menu G
H. Manufacturer
Service menu Gf
d. Working log
f. Service settings
e. Communicate config.
Service menu Gfc
a. Working hour set
c. Thermoregulation
b. Probe adjustment
S. Configuration Gfc8
Sensor present :
Multi Input 1 : NO
Multi Input 2 : NO
G. Service
Gf. Service settings
Gfc. Thermoregulation
Gfc8. S. Configuration
Change the required
Multi Input to “
YES
”
3.2.3
Configure the Multi Input assigned to the Compressors to 0-10VDC stage control and Probe type to 0-10V.
NOTE:
◦
Example shown below is for Compressors with external input assigned to Multi Input 2:
Display Progression:
G. Service
F. Alarm History
Main Menu G
H. Manufacturer
Service menu Gf
d. Working log
f. Service settings
e. Communicate config.
Service menu Gfc
a. Working hour set
c. Thermoregulation
b. Probe adjustment
S. Configuration Gfc8
Sensor present :
Multi Input 1 : NO
Multi Input 2 YES
0 - 10v STAGE CONT.
Probe type: 0 - 10V
*
*
G. Service
Gf. Service settings
Gfc. Thermoregulation
Gfc8. S. Configuration
Change to
*
0-10v STAGE CONT
*
Change Probe type
to
0-10V
NOTE: The Compressors are now configured/ready to be controlled through the external 0-10VDC input.
3.2.4
Connect the 0-10VDC staging supply to the configured Multi Input (refer to Unit’s wiring diagram).
3.2.5
Turn On the unit through the Control Interface and provide the required compressor capacity through
the 3rd Party controller 0-10VDC.
Examples of equivalent voltage and capacity scaling are as follows:
◦
3V = 33% capacity (stage 1)
◦
6V = 66% capacity (stage 2)
◦
9V = 100% capacity (stage 3)
NOTES:
◦
The Heat / Cool change over can be controlled by providing a 24VAC digital input to the controller through
the terminal of the control box (refer to wiring diagram).
◦
Ensure that the Control Interface is set for "AUTO CHANGE OVER" (under menu
C1
mode of operation).
◦
The requested external capacity value will be displayed on the status menu as Voltage x 100.
e.g. 3.3 volts will be seen as 330 on the capacity status screen.
Display Progression:
A. On / Off Unit
B. Setpoint
C. Mode of Operation
Main Menu A
D. Clock
E. Status
Main Menu E
C. Mode of Operation
*
*
*
*
Input / Output E2
Analogue Inputs
Discharge 2 Temp : 13.5
o
c
Out Coil 2 Temp. : 15.9
o
c
Room temp. : 22.6
o
c
Out . Air temp. : 16.0
o
c
Ext . InFan Spd. : 590
Ext . Capacity : 330
Main Menu
E. Status
Input / Output 02
External indoor fan speed set on
the 3rd Party controller will be
displayed if External Input is set
for indoor fans
External capacity set on the Third
Party controller, as displayed on
the Control Interface
e.g. 330 = 3.3V or 33% Spd
3.3 Compressors 24VAC External Control Mode
In this mode, the Compressors are configured for request through 24VAC input from the external controller.
Configuration Procedure:
3.3.1
Ensure that the mode of operation is set to “External Input” via Service menu.
(Please see Step
3.2.1
above).
3.3.2
Connect the stage inputs to the Stage 1, 2, 3 and Heat inputs in the control box (refer to wiring diagram).
3.1.3
Make sure the Multi Input assigned to the Compressors via S.Configuration screen
Gfc8
is disabled.