39
ActronAir
is constantly seeking ways to improve the design of it’s products, therefore specifications are subject to change without notice.
Copyright © 2017 Actron Engineering Pty. Ltd.
COMPRESSORS AND INDOOR FANS MODES OF OPERATION
NOTE:
◦
Multi Input 2 (U12) can also be enabled, in lieu of Multi Input 1, if not used for other system components.
Display Progression:
G. Service
F. Alarm History
Main Menu G
H. Manufacturer
Service menu Gf
d. Working log
f. Service settings
e. Communicate config.
Service menu Gfc
a. Working hour set
c. Thermoregulation
b. Probe adjustment
S. Configuration Gfc8
Sensor present :
Multi Input 1 YES
Multi Input 2 : NO
G. Service
Gf. Service settings
Gfc. Thermoregulation
Gfc8. S. Configuration
Change
Multi Input 1 to
“
Yes
”
4.2.3
Configure Multi Input 1 (or Multi Input 2) to 0-10VDC Fan Speed and Probe type to 0-10V:
Display Progression:
G. Service
F. Alarm History
Main Menu G
H. Manufacturer
Service menu Gf
d. Working log
f. Service settings
e. Communicate config.
Service menu Gfc
a. Working hour set
c. Thermoregulation
b. Probe adjustment
S. Configuration Gfc8
Sensor present :
Multi Input 1 : YES
0 - 10v IN FAN SPD.
Probe type: 0 - 10V
Multi Input 2 : NO
*
*
G. Service
Gf. Service settings
Gfc. Thermoregulation
Gfc8. S. Configuration
Change to
0-10v IN FAN SPD
Change Probe type
to
0-10V
4.2.4
Set the Supply Fan type to “VARI SPEED” via S.Configuration screen
Gfc13
:
Display Progression:
G. Service
F. Alarm History
Main Menu G
H. Manufacturer
Service menu Gf
d. Working log
f. Service settings
e. Communicate config.
Service menu Gfc
a. Working hour set
c. Thermoregulation
b. Probe adjustment
S. Configuration Gfc13
Type of fans fitted :
Supply : VARI SPEED
Outdoor : 2 SPEED AC
Econ. cycle fitted : Yes
Econ. Type: Modulate
G. Service
Gf. Service settings
Gfc. Thermoregulation
Gfc13. S. Configuration
Change to
VARI SPEED
4.2.5
Set the Supply Fan Control to “External” via S.Configuration screen
Gfc11
:
Display Progression:
G. Service
F. Alarm History
Main Menu G
H. Manufacturer
Service menu Gf
d. Working log
f. Service settings
e. Communicate config.
Service menu Gfc
a. Working hour set
c. Thermoregulation
b. Probe adjustment
S. Configuration Gfc11
Unit control mode :
EXTERNAL INPUT
Supply Fan Control :
EXTERNAL
Select Wall Control:
SINGLE CL01
G. Service
Gf. Service settings
Gfc. Thermoregulation
Gfc11. S. Configuration
Set to “
EXTERNAL
”
NOTE: The Indoor Fans are now configured/ready to be controlled through external 0-10VDC input.
4.2.6
Connect the 0-10VDC supply to the configured Multi Inputs 1 (refer to wiring diagram).
4.2.7
Turn On the unit through the Control Interface and set the required indoor fan voltage
through the 3rd Party controller 0-10VDC input.
NOTES:
◦
Refer to item
5.0 Indoor Fan Operation Modes
for configuring the Indoor Fans in either "Continuous
Mode" or "Auto Mode".
◦
If there is no voltage supplied to the indoor fan and it is selected as continuous, the fan will run on the
minimum speed for the selected unit model when the unit is On.
◦
The requested external fan speed value will be displayed on the status menu as Voltage x 100.
e.g. 5.9 volts will be displayed as 590 on the capacity screen.
Display Progression:
D. Clock
E. Status
Main Menu E
C. Mode of Operation
*
*
*
*
Input / Output E2
Analogue Inputs
Discharge 2 Temp : 13.5
o
c
Out Coil 2 Temp. : 15.9
o
c
Room temp. : 22.6
o
c
Out . Air temp. : 16.0
o
c
Ext . InFan Spd. : 590
Ext . Capacity : 330
E. Status
E2. Input / Output
External indoor fan speed set
on the 3rd Party controller, as
displayed on Control Interface
e.g. 590 = 5.9V or 59% Spd