PointSource and WideArray Edge Detectors
58
1) After pressing the Calibrate button on the Detector Settings screen, the Calibration screen will
appear.
2) Make sure that the edge detector to be calibrated is completely clear of web material or any other
obstruction, and then press Calibrate Detector button.
During the calibration the number displayed in the Lowest Beam box will count down to 1. Then
the Lowest Beam box will show a number between 100 and 204.
3) Place the web material that is being calibrated in the detector gap and completely cover the
transducer area. Press the Calibrate Material button. The Opacity box will show a number
between 0 and 100. This number represents the opacity of the web material.
Important:
Keep the web material at least 0.25” [6mm] from either transducer during
calibration.
4) Remove the web material from the detector and wait for 15 seconds before guiding.
The edge detector is now calibrated.
Summary of Contents for EVO 150
Page 1: ...P O Box 7816 Madison Wisconsin 53707 7816 Instruction Manual EVO 150 Web Guide Control System...
Page 2: ......
Page 6: ...EVO 150 Controller 4 EVO 150TM Web Guide Control System...
Page 56: ...PointSource and WideArray Edge Detectors 54 PointSource and WideArray Edge Detectors...
Page 62: ...AccuBeam 3 Digital Line Guide Sensor 60 AccuBeam 3 Digital Line Guide Sensor...
Page 85: ...AccuWeb Linear Actuators 83 AccuWeb Linear Actuators...
Page 90: ...Remote Station Guide Point Adjust 88 Remote Station Guide Point Adjust...
Page 99: ...Remote Station Auxiliary 97 Remote Station Auxiliary...
Page 104: ...Fieldbus Interface 102 Fieldbus Interface...
Page 124: ......
Page 125: ......
Page 126: ......
Page 127: ......
Page 128: ......
Page 129: ......
Page 130: ......
Page 131: ......
Page 132: ......
Page 133: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 137: ...NOTES...