4.7 ADAPTATION TO USE OF OTHER GASES AND BURNER REGULATION

The boilers are produced for the type of gas specifically 

requested when ordering, which is shown on packing plate 

and on the boiler technical data plate.

Any  subsequent  transformations  must  be  carried  out 

strictly  by  qualified  personnel,  who  will  use  the 

appropriately  prepared  accessories  by  the  manufacturer 

and  will  carry  out  the  modification  operations  and  the 

adjustments needed for good tuning.

4.7.1. TRANSFORMATIONS FROM METHANE TO LPG

Change parameter P02 from 0 to 1.

Place the LPG adjustment label on the boiler.

Check and if necessary modify the parameters P08, P09, P31, 

P32  and  P33  according  to  what  is  indicated  in  the  table  of 

parameters.

PARAMETER ACCESS

Simultaneously pressing, for the cycle time, the keys "RESET" 

and

 

"

    

" You enter the parameter programming mode.

 

The 

display shows "tS" for 1 sec, then the P number of

 

TSP for 1 sec 

and then the value for 3 sec.

 

The first modifiable parameter 

corresponds to P01.

 

Press the 

   

 

   

or 

     

 button to select the 

desired parameter.

 

Pressing, for the cycle time, the  

       

key 

enables the function of

 

modification of the selected parameter.

 

The previously set value appears on the display.

 

Pressing the

 

 

   

 

or 

    

 keys changes the value of the parameter

 

selected.

 

Pressing the "

  

 button for the cycle time saves the new one

 

setting.

 

Simultaneously pressing, for the cycle time, the keys 

"RESET"and

 

     

Exits in parameter programming mode.

 

Proceed 

with combustion regulation (CO2).

4.7.2. GAS TO METHANE TRANSFORMATIONS

Change parameter P02 from 1 to 0.

 

Place the label indicating the 

adjustment on the boiler a

 

Methane.Check and if necessary 

modify the parameters P08, P09, P31, P32 and

 

P33 in 

accordance with Table 24.

PARAMETER ACCESS

Simultaneously pressing, for the cycle time, the keys "RESET" 

and

 

"" You enter the parameter programming mode.

 

The display 

shows "tS" for 1 sec, then the P number of

 

TSP for 1 sec and 

then the value for 3 sec.

 

The first modifiable parameter 

corresponds to P01.

 

Press the "" or "" button if the desired 

parameter is selected.

 

Pressing, for the cycle time, the "" key 

enables the function of

 

modification of the selected parameter.

 

The previously set value appears on the display.

 

Pressing the "" 

or "" keys changes the value of the parameter

 

selected.

 

Pressing 

the "" button for the cycle time saves the new one

 

setting.

 

Simultaneously pressing, for the cycle time, the "RESET" keys

 

and "" you exit the parameter programming mode.

 

Proceed with 

combustion regulation (CO2).

 

4.7.3. CHECK AND ADJUSTMENT OF THE GAS VALVE

PREMISE

 

The boiler, by means of the "BEST" function, is 

suitable

 

automatically combustion according to the conditions

 

of 

installation, therefore the following procedure is to be carried out

 

following the chimney sweep function if the calibration values

 

gas 

were not corresponding to those on the plate or if yes

 

the 

electronic board, the electrode, the fan or the

 

gas valve.

 

The 

boiler must be ready for operation, purged

 

from the air and with 

heating function enabled.

 

The procedure can start in two different 

ways depending on

 

of the value of the parameter "P14":

 

AUTO 

("P14" = 5): the boiler performs 10 ignition attempts a

 

powers 

gradually increasing;

MANU

 (“P14” = 0): la caldaia esegue 5 tentativi di accensione 

alla potenza di accensione indicata nel parametro “P31”.

Una volta ottenuta con successo l’accensione del bruciatore, la 

caldaia esegue in autonomia un ciclo alla potenza minima “P0”, 

di  accensione  “P1”  e  alla  potenza  massima  “P2”  per  ottenere 

una buona stabilità di fiamma, poi si porta in modalità di modifica 

della CO2 per permettere la taratura manuale.

L’impostazione  del  tipo  di  modalità  (AUTO  o  MANU)  viene 

immessa  nel  codice  di  attivazione  per  il  parametro  “P14”  nel 

menù Parametri TSP.

Parametri TSP impostabili da interfaccia e da Comando Remoto.

La  modalità AUTO  è  quella  consigliata  e  che  permette  la  più 

ampia libertà di modifica della CO2.

Mixer

Gas tube

Valvola gas

OPERATIONS TO BE PERFORMED

Enter the chimney sweep function and check that the value

of CO2 falls within the limits of Table 11 both at maximum (Hi) 

that to the minimum (Lo) power (if the temperature of the plant 

should it rise too high, it is possible to open the taps

ACS to dispose of the heat; the procedure cannot be started

with the ACS open).

If this is not the case, proceed as described below.

Press the "MODE" keys simultaneously for the cycle time 

 

MODE

 ”

 

e “ 

RESET

 ”. 

Release then press immediately (within 2 seconds) 

one time      

 .

The card confirms the activation of the function and displays

 

on 

the "Au-to" or "Ma-nu" display depending on the mode

 

defined 

setting.

 

The card will internally generate an operation request

 

in 

“calibration” mode and the ignition sequence will start.

 

If the "Au-

to" function is active, the flashing is also activated

 

of the 

"radiator" symbol.

 

Once the ignition has been completed, the 

boiler

 

will perform a parameter storage cycle at maximum

 

power, then to the ignition power and, finally, to the minimum

 

power. During this phase, the LCD display cyclically displays the

 

cycle time and delivery temperature.

 

At this point the fumes 

analyzer probe can be inserted into the

 

exhaust duct.

Summary of Contents for HUB RADIATOR PACK CF 3.0

Page 1: ...ATION HUB RADIATOR PACK CF Factory made high efficiency integrated hybrid system patented heat pump with direct exchange refrigerant water to produce DHW heating and air conditioning HUB RADIATOR PACK...

Page 2: ...2...

Page 3: ...3 5 1 4 5 1 5 5 1 6 5 1 7 5 2 6 2 1 6 2 2 6 2 3 6 3 7 3 1 7 3 2 8 3 3 8 3 4 8 3 5 8 3 6 Pump Down 8 3 7 9 4 INSTALLATION OF INDOOR UNITS 10 4 1 Choosing the place of installation 10 4 2 Technical data...

Page 4: ...tructions 27 9 5 General system checks 27 10 START UP 27 10 1 First start up checks 27 10 2 Starting up 27 11 REPAIR COMPONENTS REPLACEMENTS 27 11 1 Refrigerant circuit 27 11 2 Drying and vacuum of th...

Page 5: ...be installed at wall or recessed the indoor unit is supplied complete with all the appropriate ones internal copper exchangers R410A refrigerant gas connections DHW connections air vent valve safety v...

Page 6: ...2 x 0 75 mm 2 x 2 20 A curv D Table 2 Tightening torque Torque Tightening min max N m 1 4 14 18 3 8 33 42 5 8 63 77 Table 3 Refrigerant charge m Max Add refrigerant quantity g m HR 3 0 5 15 5 20 HR 7...

Page 7: ...not compromise the product operation and or personal safety e of assets Make sure that the space at the back of the unit is greater than 30 cm The front must have more than 60 cm of space Ensure that...

Page 8: ...at each tube both the gas side tubes and the liquid between internal group and external group has been connected in the correct way and that all the wiring necessary for the testing have been carried...

Page 9: ...pressure gauge using the refrigerant gas Completely close the liquid valve Turn on the machine in cooling mode When the pressure of the pressure gauge goes from 0 to 0 5 kg 2G cm between 14 2 and 7 1...

Page 10: ...as connection 19 Gas connection R410A 5 8 4 1 CHOICE OF INSTALLATION SITE OF THE HYBRID SYSTEM When determining where to install the internal unit of the system hybrid HUB RADIATOR PACK CF take the fo...

Page 11: ...that the support surface is regular Use the bracket as a template and mark the position of the holes from to achieve x 3 Wilo Yonos Pico 25 18 60 4 5 7 5 4 75 4 6 3 4 3 4 1 2 1 2 230V 1 50Hz 1447 720...

Page 12: ...pipes the weight of which must not burden on the appliance properly insulate the pipes to find the right ones heat losses H Connect a special safety drain in correspondence of the 1 2 female threaded...

Page 13: ...or exclude them safety devices In the event of repeated shutdowns of the boiler it is necessary have the air intake flue gas exhaust ducts checked which may be blocked or inadequate for the disposal o...

Page 14: ...tion that the total path of the fumes from the exit point of the same from the terminal to their outlet from the external perimeter of the balcony including the height of the eventual balustrade of pr...

Page 15: ...temperatura di spegnimento dopo accensione bruciatore 0 20 0 DO NOT MODIFY THIS VALUE P61 Selezione allarme temperatura scarico fumi 20 150 105 P62 Not used P63 Not used P64 Not used P65 Anti legionel...

Page 16: ...0 1 1 DO NOT MODIFY P20 Selection of the minimum value of the DHW 35 50 35 P21 Low temperature zone selection 0 1 0 0 High temperature 1 Low temperature P22 Not used P23 Selection of pump activation t...

Page 17: ...bustion regulation CO2 4 7 3 CHECK AND ADJUSTMENT OF THE GAS VALVE PREMISE The boiler by means of the BEST function is suitable automatically combustion according to the conditions of installation the...

Page 18: ...s specified below Control operations general check of the integrity of the boiler check the tightness of the gas circuit of the boiler and the gas supply network to the boiler control of the boiler su...

Page 19: ...s network and the electricity grid The materials of which the boiler is made are all recyclable Once dismantled the boiler must be disposed of in compliance of the legislation in force in the country...

Page 20: ...o use the boiler only it is necessary to set IC to ON and set DC to EMERGENCY Simultaneously put the CD control in STAND BY by pressing the SUN button Booster terminal board Technical water probe Boos...

Page 21: ...the integration boiler it is necessary to set IC to ON and set DC to INTEGRATION In this way the control unit will decide when the help of the boiler is needed which will work in support of the heat...

Page 22: ...12 3 03 2 91 10 3 45 3 37 3 29 3 20 3 10 2 98 11 3 55 3 46 3 37 3 28 3 18 3 06 12 3 64 3 55 3 45 3 36 3 25 3 13 13 3 75 3 64 3 54 3 44 3 33 3 20 14 3 85 3 74 3 63 3 52 3 41 3 28 15 3 95 3 83 3 72 3 6...

Page 23: ...ting C 30 35 40 45 50 55 1 074 10 2 96 2 59 2 25 1 91 1 59 1 27 HR 3 0 9 3 04 2 67 2 32 1 98 1 65 1 33 8 3 14 2 75 2 39 2 05 1 71 1 39 7 3 23 2 84 2 47 2 12 1 78 1 46 6 3 32 2 92 2 54 2 19 1 84 1 52 5...

Page 24: ...cold water filter 19 Secondary plate heat exchanger 20 Domestic hot water temperature sensor 21 Automatic by pass integrated on plate heat exchanger 22 Motorized 3 way valve S Condensate drain G Gas i...

Page 25: ...an speed x100 TMax operating temperature in heating mode Total expansion vessel capacity 6 5 TECHNICAL FEATURES BOILER HUB RADIATOR PACK CF TECHNICAL FEATURES kW bar bar bar bar l min V Hz A W IP Kg m...

Page 26: ...d mode with the active boiler for DHW production and external booster in active heat pump to produce chilled water up to 4 C per power the hydronic terminals IC ON OFF O I CD 2 0 0 1 2 3 4 5 H m 4 6 8...

Page 27: ...UP Before proceeding with the commissioning of the appliance you need to make sure that the safety conditions and all the provisions listed in this manual has been complied with the fixing to the sup...

Page 28: ...inants that have been must be eliminated introduced to clean the circuit or to effect the operations carried out WARNING Do not inhale the refrigerant vapors coming from burned compressors as it can b...

Page 29: ...as to obtain a temperature of system delivery that increases in a way proportional to decreasing air temperature external To proceed with this function set the value of the parameter ST08 and ST03 at...

Page 30: ...ler Boiler differential boiler Boiler activation delay time boiler SET POINT external air compressor deactivation Compressor activation external air differential PARAMETERS OF ALARMS FUNCTIONS Probe f...

Page 31: ...bled but not active the icon is off ___________________________________________________ On during access to the functions menui ___________________________________________________ Lit if the resistanc...

Page 32: ...ws exit from parameter programming 2 contemporary pressure prolonged keys allows entry into manual defrost ___________________________________________________ Remote terminal Regarding the use of the...

Page 33: ...ure falls below 90 C P1 probe alarm PB1 probe alarm PB2 probe alarm PB3 faulty probe or resistive value out of range faulty probe or resistive value out of range probe alarm PB4 faulty probe or resist...

Page 34: ...al probe 3 Substitution of tract 1 Replacement of the outdoor unit probe 2 Connection cable replacement external probe 3 Substitution of tract 1 Thermostat replacement 2 External booster recharge 3 co...

Page 35: ...int ST21 Set massimo ambiente in chiller ST18 110 230 C F Dec int ST22 Set point ambiente in p d c ST24 ST25 C F dec int ST23 Differenziale ambiente in p d c 0 0 0 25 0 45 C F Dec int ST24 Set minimo...

Page 36: ...pen contact 0 1 CF16 Polarity ID5 0 Active close contact 1 Active open contact 0 1 ventilatore di mandata 13 Allarme termica pompa acqua condensatore 14 Flussostato condensatore CF09 CONFIGURATION ID2...

Page 37: ...sent 1 Continuous operation in ON OFF output 2 Operation on compressor request 3 Continuous output operation 4 20mA 4 Operation on request of the compressor 4 20mA 0 4 CO12 Compressor 0 Enabled 1 OFF...

Page 38: ...6 Minimum defrost alarm 0 Not enabled 1 Enabled 0 1 dF17 Minimum alarm delay when reversing the 4 way valve 0 250 Sec FA09 Maximum fan speed in summer 30 100 FA10 Minimum fan speed temperature pressur...

Page 39: ...utput relay polarity 0 Output without voltage in normal conditions with voltage in the presence of an alarm 1 Output with voltage in normal conditions without voltage in the presence of an alarm 0 1 A...

Page 40: ...CE dei prodotti comporta il controllo costante of production with the aim of guaranteeing the conformity of the appliances with the safety and performance characteristics of the verified samples The...

Page 41: ..._________ Raffrescamento estivo Produzione ACS Riscaldamento Distanza tra unit interna ed esterna max 15 m Dislivello tra unit interna ed esterna max 5 m Le tubazioni delle linee frigorifere 1 4 3 8 p...

Page 42: ..._________________________________________________________ Attenzione la mancata effettuazione del primo avviamento per cause non dipendenti dall unit comporter una seconda visita la quale sar a voi di...

Page 43: ..._____________ ___________ ________________ BOOSTER POSIZIONATO A TERRA A MURO A FINESTRA SU STAFFE ANTIVIBRANTI MENSOLE A TETTO ALTRO SU BASI A SOSPENSIONE A RINGHIERA INSTALLAZIONE CON PONTEGGIO SI N...

Page 44: ...AICO SPENTO FUNZIONAMENTO IN POMPA DI CALORE BOOSTER 1 TEMPERATURA DI EVAPORAZIONE U E C Pb3 _______ TEMPERATURA ACQUA TECNICA C Pb1 _______ NB TEMPERTATURA DI INIZIO CONDENSAZIONE C _______ Attendere...

Page 45: ...ence must be made to the natural or legal person who has purchased the Product regardless of whether the seller is A2B ACCORRONI E G or other person marketing branded products A2B ACCORRONI E G This w...

Page 46: ...rroni mediante ogni opportuna operazione di trattamento manuale ed informatico per finalit funzionali all adempimento degli obblighi derivanti dal contratto di fornitura di beni servizi da parte di Ac...

Page 47: ...provisions of the law on the subject of deduction for the energy requalification costs of the existing building heritage the A2B Accorroni E G Ltd DECLARES that the product complies with the European...

Page 48: ...corroni E G s r l Via d Ancona 37 60027 Osimo An Tel 071 723991 web site www accorroni it e mail a2b accorroni it A2B Accorroni E G S r l reserve the right to make changes without prior notice TECHNIC...

Reviews: