39
dF18
4-way reverse cycle valve
0 = ON in cooling
1 = ON in heating mode
0
1
dF19
Defrost cycle temperature / pressure set
-50.0
-58
0.0
0
110
230
50.0
725
°C
°F
bar
psi
Dec
int
Dec
int
dF20
Defrost cycle forcing differential
0.0
0
0.0
0
25.0
45
50.0
725
°C
°F
Bar
psi
Dec
Int
Dec
Int
dF21
Fan block in defrost
0
1
Pr2
Password
0
999
Parametri Allarmi
Parameters
Description
min
max
udm
Risoluzion
e
AL01
Low pressure switch delay
0
250
Sec
AL02
Maximum number of operations at low pressure hour
0
16
AL03
Low pressure alarm with compressor off
0 = Not active when the compressor is off
1 = Active when the compressor is off
0
1
AL04
Flow / thermal alarm delay delivery (unit
air / air) from pump / fan activation
0
250
Sec
AL05
AL05 Maximum time remaining for flow switch alarm before
turn into manual and lock the pump if in motion water
0
250
Sec
AL06
Duration of flow switch / thermal input supply active
0
250
Sec
AL07
Duration of flow switch / thermal input of delivery not
active
0
250
Sec
AL08
Compressor thermal alarm delay
-2
at the start
0
250
Sec
AL09
Maximum number of operations for compressors thermal time
0
16
AL10
Maximum number of interventions hour high temperature
alarm / condensing pressure
0
16
AL11
High temperature / pressure alarm set point of
condensation
-50.0
-58
0.0
0
110
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
AL12
High temperature / pressure differential
0
0
0
0
25.0
45
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
AL13
Low pressure alarm delay analog input
0
250
Sec
AL14
Low pressure alarm set point for analogue input
-50.0
-58
0.0
0
110
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
AL15
Low temperature / pressure differential
0
0
0
0
25.0
45
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
AL16
Maximum number of operations for low pressure alarm hour
analog input
0
16
AL17
Enable buzzer output and alarm relay in OFF or
stand-by
0
0 = Buzzer output and alarm relay enabled
1 = Buzzer output and alarm relay not enabled
0
1
AL18
Open collector alarm / output relay polarity
0 = Output without voltage in normal conditions, with
voltage in the presence of an alarm
1 = Output with voltage in normal conditions, without
voltage in the presence of an alarm
0
1
AL19
Probe for antifreeze alarm:
0 = Related to parameters Ar16 in chiller - Ar17 in heat pump
1 = On Pb1 probe
2 = On Pb2 probe
3 = On Pb3 probe
4 = On Pb4 probe
0
4
AL20
Maximum number of interventions now generic block alarm
unit
0
16
AL21
Generic alarm delay time for unit with input
digital active
0
250
Sec
AL22
Generic alarm delay time for unit with input
digital not active
0
250
10 sec
10 sec
AL23
Generic alarm operation
0 = signaling only does not depend on AL20 (alarm relay e
buzzer activated) always automatic reset
1 = the alarm blocks the unit the alarm reset depends on the
value of parameter AL20
0
1
AL24
System water inlet high temperature alarm set point
-50.0
-58
110
230
°C
°F
Dec
int
AL25
Inlet water high temperature alarm differential
0.1
0
25.0
45
°C
°F
Dec
int
AL26
Water inlet high temperature alarm delay
0
250
10 sec
10 sec
AL27
Maximum number of high temperature alarm time
interventions water inlet system
0
16
AL28
Delay alarm for hot side flow switch from activation /
water pump shutdown
0
250
Sec
AL29
Maximum time for hot side flow switch alarm
before turning into manual and locking, if in motion, the
water pump
0
250
Sec
AL30
Duration of flow switch entry hot side active (pump not
available working)
0
250
Sec
AL31
Warm side flow switch input not active (pump
working)
0
250
Sec
AL32
Hot side flow switch operation
0 = disabled
1 = chiller only enabled
2 = enabled only heat pump
3 = enabled chiller and heat pump.
0
3
Pr2
Password
0
999
15.2 DIGITAL CONTROL UNIT ELECTRICAL DIAGRAM
MF ID1, MF ID2, MF ID5 = multifunction digital inputs
HP ID3 = high pressure digital input
LP ID4 = low pressure digital input
MF RL2, MF RL3, MF RL4, MF RL5 = multifunction relay
Trigger signal out TK = output for connection to external module
for condensation fan control (phase cut)
Pb1, Pb2, Pb3, Pb4 = NTC analogue inputs
digital inputs Pb3 = 0.5 Vdc ratiomentric pressure transducer
MF o.c. out = configurable open collector output for the
external relay connection