background image

37

CF44

Remote display upper terminal default display

 

0 = PB1 

1 = PB2   

2 = 

Nothing

3 = PB4

4 = 

Unit real setpoint

5 = 

Unit status

6 = 

Nothing

7 = 

Nothing

8 = 

Job differential

9= 

Unit setpoint (fixed value of the parameter)

0

9

CF45

Remote display upper terminal default display

0 = PB1 

1 = PB2   

2 = PB3

3 = PB4

4 = 

Unit real setpoint

5 =

 Unit status

6 = 

Timer

7 = 

Nothing

8 = 

Job differential

9= 

Unit setpoint (fixed value of the parameter)

0

9

CF46

Display in std-by

0 =

  Displays the magnitudes of the normal display 

(

set with parameters 

CF36 e CF43)

1 = 

Displays the OFF label

2 = 

Displays the STBY label

0

2

CF47

Visualizzazione in STD-BY terminali remoti

0 =

Displays the magnitudes of the normal display

 

(

set with parameters 

 CF36 e CF43)

1 = 

Displays the OFF label

2 = 

Displays the STBY label

0

2

CF48

Analog output configuration

4..20mA / 0..10V

 

0 =

 

uscita 4..20mA

1 = uscita 0..10V  

0

1

Pr2

Password

0

999

Set Point Dinamico

Parametr

e

Description

min

max

udm

Risoluzion

e

Sd01

Dynamic setpoint

0= 

Not enabled

1= 

Enabled

0

1

Sd02

Offset max setpoint d.

summer

 

-30.0

-54

30.0

54

°C

°F

Dec

int

Sd03

Offsett max setpoint d.

winter

 

-30.0

-54

30.0

54

°C

°F

Dec

int

Sd04

Set temp. Aria esterna setpoint d. 

summer

 

-50.0

-58

110

230

°C

°F

Dec

int

Sd05

Set temp. Aria esterna setpoint d. 

winter

 

-50.0

-58

110

230

°C

°F

Dec

int

Sd06

Differential temp. Summer outdoor setpoint air

 d. 

summer

 

-30.0

-54

30.0

54

°C

°F

Dec

int

Sd07

Differential temp. Summer outdoor setpoint air

 d. 

winter

 

-30.0

-54

30.0

54

°C

°F

Dec

int

Pr2

Password

0

999

Energy Saving

Parametr

e

Description

min

max

udm

Risoluzion

e

ES01

Inizio (0÷24)

0

23.50

Min

10 min

ES02

Fine  (0÷24)

0

23.50

Min

10 min

ES03

Monday

 

0 = 

Not enabled

1=  

Enabled

0

1

ES04

Tuesday

0 = 

Not enabled

1=  

Enabled

0

1

ES05

Wednesday

 

0 =

 Not enabled

1=  

Enabled

0

1

ES06

Thursday

 

0 = 

Not enabled

1=  

Enabled

0

1

ES07

Friday

 

0 = 

Not enabled

1=  

Enabled

0

1

ES08

Saturday

 

0 = 

Not enabled

1=  

Enabled

0

1

ES09

Sunday

 

0 = 

Not enabled

1=  

Enabled

0

1

ES10

Differential increase

 set energy saving chiller

-30.0

-54

30.0

54

°C

°F

Dec

int

ES11

Differential increase 

energy saving chiller

0.1

0

25.0

45

°C

°F

Dec

int

ES12

Differential increase 

set energy saving p.d.c.

-30.0

-54

30.0

54

°C

°F

Dec

int

ES13

Differential increase 

 energy saving p.d.c.

0.1

0

25.0

45

°C

°F

Dec

int

Pr2

Password

0

999

Compressor parameters

Parametr

e

Descrizione

min

max

udm

Risoluzion

e

CO01

Min ignition time

0

250

Sec

10Sec

CO02

Min shutdown time

0

250

Sec

10Sec

CO03

Power on delay between the two compressors

 / 

partialization

1

250

Sec

CO04

Switch-off delay between the two compressors / capacity 

control

0

250

Sec

CO05

Switch-on delay for compressors from power ON

0

250

Sec

10Sec

CO06

Compressor ON delay from pump start / supply fan

1

250

Sec

CO07

Delay OFF pump / supply fan from

0

250

Sec

CO08

compressor shutdown

0= 

Enabled

1= 

Fixed sequence

0

1

CO09

Delay time for deactivation of the water side valve from OFF

compressor

0

250 

Sec

CO10

Partition valve polarity

 

0=. Parzializzazione. ON

1=. Parzializzazione. OFF

0

1

CO11

Pump / supply fan operating mode

0= 

Absent

1= 

Continuous operation in ON / OFF output

2= 

Operation on compressor request

3= 

Continuous output operation 4 • • 20mA

4=

 Operation on request of the compressor 4 • • 20mA

0

4

CO12

Compressor

0 = 

Enabled

1 = OFF

0

1

CO13

Compressor 2 / partialization. 

0 = 

Enabled

1=  OFF

0

1

CO14

SET 

Compressor hour counter 

 1

0

999

Hr

10 Hr

CO15

SET 

Compressor hour counter 

 2

0

999

Hr

10 Hr

CO16

SET 

Water pump hour counter / supply fan (unit

air / air)

0

999

Hr

10 Hr

Evaporator unloading

CO17

Evaporator unloading activation set point 

-50.0

-58

110

230

°C

°F

Dec

int

CO18

Evaporator unloading 

0.1

0

25.0

45

°C

°F

Dec

int

CO19

Evaporator unloading activation 

0

250

Sec

10 Sec

CO20

Maximum stay time in unloading operation

comp from high temp. evaporator input

0

250

Sec

10 Sec

Capacitor unloading

CO21

Set point for compressor pressure unloading in

chiller operation

0.0

0

50.0

725

Bar

Psi

Dec

int

CO22

Pressure compressor unloading differential in

chiller operation

0.0

0

12.0

174

Bar

Psi

Dec

int

CO23

Set point for compressor pressure unloading in

heat pump operation

0.0

0

50.0

725

Bar

Psi

Dec

int

CO24

Pressure compressor unloading differential in

heat pump operation

0.0

0

12.0

174

Bar

Psi

Dec

int

CO25

Maximum time of condenser unloading 

0

250

Sec 

10 Sec

Pompa acqua condensatore

CO26

Condenser water pump operating mode

0= 

absent

1= 

Continuous operation

2= 

Operation on compressor request

0

2

CO27

OFF condenser water pump OFF delay

compressor

0

250

Sec

CO28

SET 

condenser water pump hour counter

0

999

Hr

10 Hr

Tandem compressor function

CO29

Maximum continuous operation time

compressor

Compressor start delay time from request

water side solenoid valve.

0

250

Min

CO30

0

250

sec

10 Sec 

Modulating evaporator water pump

CO31

System pump pickup time at maximum speed from

thermoregulation request

0

250

sec

CO32

Minimum speed% in operation with active compressor

(Chiller)

30

100

%

CO33

Minimum speed% in operation with active compressor

(Heat pump)

30

100

%

CO34

Speed% system pump with compressor

30

100

%

CO35

Pump speed control set point according to the

outlet water temperature (PB2) in chiller mode

-50.0

-58

110

230

°C

°F

Dec

int

CO36

Water temperature control band sent in chiller 0.0

0.0

0

25.0

45

°C

°F

Dec

int

CO37

Delay delay time comp. from thermoregulation with

water pump <100% in chiller operation

0

250

sec

CO38

Pump speed control set point depending on the

supply water temperature (PB2) in pump mode heat

-50.0

-58

110

230

°C

°F

Dec

int

CO39

Water temperature control band in heat pump

0.0

0

25.0

45

°C

°F

Dec

int

CO40

Time delay for switching off comp. from thermoregulation with

water pump <100% in operation heat pump

0

250

sec

Pr2

Password

0

999

Parametri Ventilazione

Parameter 

Description 

min

max

udm

Risolu

tion

FA01

Fan output

0= 

absent

1= Present

0

1

FA02

Fan adjustments

0 = On with compressor switched on

1 = ON / OFF adjustment

2 = Proportional speed regulator

0

2

FA03

FA03 Fan operation mode

0 = Dependent on the compressor

1 = Independent from the compressor

0

1

FA04

Max speed start-up time after 

ON

0

250

Sec

FA05

Fan offset 

0

20

Micro

Sec

250

• •

s

FA06

Not used

FA07

Pre-ventilation in cooling before compressor 

0

250

Sec

FA08

Minimum fan speed in summer 

30

100

%

Summary of Contents for HUB RADIATOR PACK CF 3.0

Page 1: ...ATION HUB RADIATOR PACK CF Factory made high efficiency integrated hybrid system patented heat pump with direct exchange refrigerant water to produce DHW heating and air conditioning HUB RADIATOR PACK...

Page 2: ...2...

Page 3: ...3 5 1 4 5 1 5 5 1 6 5 1 7 5 2 6 2 1 6 2 2 6 2 3 6 3 7 3 1 7 3 2 8 3 3 8 3 4 8 3 5 8 3 6 Pump Down 8 3 7 9 4 INSTALLATION OF INDOOR UNITS 10 4 1 Choosing the place of installation 10 4 2 Technical data...

Page 4: ...tructions 27 9 5 General system checks 27 10 START UP 27 10 1 First start up checks 27 10 2 Starting up 27 11 REPAIR COMPONENTS REPLACEMENTS 27 11 1 Refrigerant circuit 27 11 2 Drying and vacuum of th...

Page 5: ...be installed at wall or recessed the indoor unit is supplied complete with all the appropriate ones internal copper exchangers R410A refrigerant gas connections DHW connections air vent valve safety v...

Page 6: ...2 x 0 75 mm 2 x 2 20 A curv D Table 2 Tightening torque Torque Tightening min max N m 1 4 14 18 3 8 33 42 5 8 63 77 Table 3 Refrigerant charge m Max Add refrigerant quantity g m HR 3 0 5 15 5 20 HR 7...

Page 7: ...not compromise the product operation and or personal safety e of assets Make sure that the space at the back of the unit is greater than 30 cm The front must have more than 60 cm of space Ensure that...

Page 8: ...at each tube both the gas side tubes and the liquid between internal group and external group has been connected in the correct way and that all the wiring necessary for the testing have been carried...

Page 9: ...pressure gauge using the refrigerant gas Completely close the liquid valve Turn on the machine in cooling mode When the pressure of the pressure gauge goes from 0 to 0 5 kg 2G cm between 14 2 and 7 1...

Page 10: ...as connection 19 Gas connection R410A 5 8 4 1 CHOICE OF INSTALLATION SITE OF THE HYBRID SYSTEM When determining where to install the internal unit of the system hybrid HUB RADIATOR PACK CF take the fo...

Page 11: ...that the support surface is regular Use the bracket as a template and mark the position of the holes from to achieve x 3 Wilo Yonos Pico 25 18 60 4 5 7 5 4 75 4 6 3 4 3 4 1 2 1 2 230V 1 50Hz 1447 720...

Page 12: ...pipes the weight of which must not burden on the appliance properly insulate the pipes to find the right ones heat losses H Connect a special safety drain in correspondence of the 1 2 female threaded...

Page 13: ...or exclude them safety devices In the event of repeated shutdowns of the boiler it is necessary have the air intake flue gas exhaust ducts checked which may be blocked or inadequate for the disposal o...

Page 14: ...tion that the total path of the fumes from the exit point of the same from the terminal to their outlet from the external perimeter of the balcony including the height of the eventual balustrade of pr...

Page 15: ...temperatura di spegnimento dopo accensione bruciatore 0 20 0 DO NOT MODIFY THIS VALUE P61 Selezione allarme temperatura scarico fumi 20 150 105 P62 Not used P63 Not used P64 Not used P65 Anti legionel...

Page 16: ...0 1 1 DO NOT MODIFY P20 Selection of the minimum value of the DHW 35 50 35 P21 Low temperature zone selection 0 1 0 0 High temperature 1 Low temperature P22 Not used P23 Selection of pump activation t...

Page 17: ...bustion regulation CO2 4 7 3 CHECK AND ADJUSTMENT OF THE GAS VALVE PREMISE The boiler by means of the BEST function is suitable automatically combustion according to the conditions of installation the...

Page 18: ...s specified below Control operations general check of the integrity of the boiler check the tightness of the gas circuit of the boiler and the gas supply network to the boiler control of the boiler su...

Page 19: ...s network and the electricity grid The materials of which the boiler is made are all recyclable Once dismantled the boiler must be disposed of in compliance of the legislation in force in the country...

Page 20: ...o use the boiler only it is necessary to set IC to ON and set DC to EMERGENCY Simultaneously put the CD control in STAND BY by pressing the SUN button Booster terminal board Technical water probe Boos...

Page 21: ...the integration boiler it is necessary to set IC to ON and set DC to INTEGRATION In this way the control unit will decide when the help of the boiler is needed which will work in support of the heat...

Page 22: ...12 3 03 2 91 10 3 45 3 37 3 29 3 20 3 10 2 98 11 3 55 3 46 3 37 3 28 3 18 3 06 12 3 64 3 55 3 45 3 36 3 25 3 13 13 3 75 3 64 3 54 3 44 3 33 3 20 14 3 85 3 74 3 63 3 52 3 41 3 28 15 3 95 3 83 3 72 3 6...

Page 23: ...ting C 30 35 40 45 50 55 1 074 10 2 96 2 59 2 25 1 91 1 59 1 27 HR 3 0 9 3 04 2 67 2 32 1 98 1 65 1 33 8 3 14 2 75 2 39 2 05 1 71 1 39 7 3 23 2 84 2 47 2 12 1 78 1 46 6 3 32 2 92 2 54 2 19 1 84 1 52 5...

Page 24: ...cold water filter 19 Secondary plate heat exchanger 20 Domestic hot water temperature sensor 21 Automatic by pass integrated on plate heat exchanger 22 Motorized 3 way valve S Condensate drain G Gas i...

Page 25: ...an speed x100 TMax operating temperature in heating mode Total expansion vessel capacity 6 5 TECHNICAL FEATURES BOILER HUB RADIATOR PACK CF TECHNICAL FEATURES kW bar bar bar bar l min V Hz A W IP Kg m...

Page 26: ...d mode with the active boiler for DHW production and external booster in active heat pump to produce chilled water up to 4 C per power the hydronic terminals IC ON OFF O I CD 2 0 0 1 2 3 4 5 H m 4 6 8...

Page 27: ...UP Before proceeding with the commissioning of the appliance you need to make sure that the safety conditions and all the provisions listed in this manual has been complied with the fixing to the sup...

Page 28: ...inants that have been must be eliminated introduced to clean the circuit or to effect the operations carried out WARNING Do not inhale the refrigerant vapors coming from burned compressors as it can b...

Page 29: ...as to obtain a temperature of system delivery that increases in a way proportional to decreasing air temperature external To proceed with this function set the value of the parameter ST08 and ST03 at...

Page 30: ...ler Boiler differential boiler Boiler activation delay time boiler SET POINT external air compressor deactivation Compressor activation external air differential PARAMETERS OF ALARMS FUNCTIONS Probe f...

Page 31: ...bled but not active the icon is off ___________________________________________________ On during access to the functions menui ___________________________________________________ Lit if the resistanc...

Page 32: ...ws exit from parameter programming 2 contemporary pressure prolonged keys allows entry into manual defrost ___________________________________________________ Remote terminal Regarding the use of the...

Page 33: ...ure falls below 90 C P1 probe alarm PB1 probe alarm PB2 probe alarm PB3 faulty probe or resistive value out of range faulty probe or resistive value out of range probe alarm PB4 faulty probe or resist...

Page 34: ...al probe 3 Substitution of tract 1 Replacement of the outdoor unit probe 2 Connection cable replacement external probe 3 Substitution of tract 1 Thermostat replacement 2 External booster recharge 3 co...

Page 35: ...int ST21 Set massimo ambiente in chiller ST18 110 230 C F Dec int ST22 Set point ambiente in p d c ST24 ST25 C F dec int ST23 Differenziale ambiente in p d c 0 0 0 25 0 45 C F Dec int ST24 Set minimo...

Page 36: ...pen contact 0 1 CF16 Polarity ID5 0 Active close contact 1 Active open contact 0 1 ventilatore di mandata 13 Allarme termica pompa acqua condensatore 14 Flussostato condensatore CF09 CONFIGURATION ID2...

Page 37: ...sent 1 Continuous operation in ON OFF output 2 Operation on compressor request 3 Continuous output operation 4 20mA 4 Operation on request of the compressor 4 20mA 0 4 CO12 Compressor 0 Enabled 1 OFF...

Page 38: ...6 Minimum defrost alarm 0 Not enabled 1 Enabled 0 1 dF17 Minimum alarm delay when reversing the 4 way valve 0 250 Sec FA09 Maximum fan speed in summer 30 100 FA10 Minimum fan speed temperature pressur...

Page 39: ...utput relay polarity 0 Output without voltage in normal conditions with voltage in the presence of an alarm 1 Output with voltage in normal conditions without voltage in the presence of an alarm 0 1 A...

Page 40: ...CE dei prodotti comporta il controllo costante of production with the aim of guaranteeing the conformity of the appliances with the safety and performance characteristics of the verified samples The...

Page 41: ..._________ Raffrescamento estivo Produzione ACS Riscaldamento Distanza tra unit interna ed esterna max 15 m Dislivello tra unit interna ed esterna max 5 m Le tubazioni delle linee frigorifere 1 4 3 8 p...

Page 42: ..._________________________________________________________ Attenzione la mancata effettuazione del primo avviamento per cause non dipendenti dall unit comporter una seconda visita la quale sar a voi di...

Page 43: ..._____________ ___________ ________________ BOOSTER POSIZIONATO A TERRA A MURO A FINESTRA SU STAFFE ANTIVIBRANTI MENSOLE A TETTO ALTRO SU BASI A SOSPENSIONE A RINGHIERA INSTALLAZIONE CON PONTEGGIO SI N...

Page 44: ...AICO SPENTO FUNZIONAMENTO IN POMPA DI CALORE BOOSTER 1 TEMPERATURA DI EVAPORAZIONE U E C Pb3 _______ TEMPERATURA ACQUA TECNICA C Pb1 _______ NB TEMPERTATURA DI INIZIO CONDENSAZIONE C _______ Attendere...

Page 45: ...ence must be made to the natural or legal person who has purchased the Product regardless of whether the seller is A2B ACCORRONI E G or other person marketing branded products A2B ACCORRONI E G This w...

Page 46: ...rroni mediante ogni opportuna operazione di trattamento manuale ed informatico per finalit funzionali all adempimento degli obblighi derivanti dal contratto di fornitura di beni servizi da parte di Ac...

Page 47: ...provisions of the law on the subject of deduction for the energy requalification costs of the existing building heritage the A2B Accorroni E G Ltd DECLARES that the product complies with the European...

Page 48: ...corroni E G s r l Via d Ancona 37 60027 Osimo An Tel 071 723991 web site www accorroni it e mail a2b accorroni it A2B Accorroni E G S r l reserve the right to make changes without prior notice TECHNIC...

Reviews: