36
CF17
Polarit
y
PB1
0=
Active close contact
1=
Active open contact
0
1
CF18
Polarit
y
PB2
0=
Active close contact
1=
Active open contact
0
1
CF19
Polarit
y
PB4
0=
Active close contact
1=
Active open contact
0
1
CF20
Configura
tion
RL4
0 =
Alarm relay
1 =
Compressor capacity control 1
2 =
Compressor No. 2
3 = ON/OFF
ventilation
4 =
Reversing valve
5 =
Antifreeze / support resistance n ° 1
6 =
Water side solenoid
7 =
Water side solenoid only in heat pump
8=
Antifreeze / support resistance n ° 2
9
=
Evaporator water pump / supply fan
(air / air machines)
10=
Condenser water pump
0
10
CF21
Configuration
RL5
0 = Alarm relay
1 = Compressor capacity control 1
2 = Compressor No. 2
3 = ON/OFF ventilation
4 = Reversing valve
5 = Antifreeze / support resistance n ° 1
6 = Water side solenoid
7 = Water side solenoid only in heat pump
8= Antifreeze / support resistance n ° 2
9 = Evaporator water pump / supply fan
(air / air machines)
10= Condenser water pump
0
10
CF22
Pressure value at
4mA / 0,5V
0.0
0
50.0
725
Bar
Psi
Dec
int
CF23
Pressure value at
20mA / 5V
0.0
0
50.0
725
Bar
Psi
Dec
int
CF24
Offset PB1
-12.0
-21
12.0
21
°C
°F
Dec
int
CF25
Offset PB2
-12.0
-21
12.0
21
°C
°F
Dec
int
CF26
Offset PB3
-12.0
-21
-12.0
-174
12.0
21
12.0
174
°C
°F
Bar
Psi
Dec
int
dec
int
CF17
Polarità PB1
0= Attivo contatto chiuso
1= Attivo contatto aperto
0
1
CF18
Polarità PB2
0= Attivo contatto chiuso
1= Attivo contatto aperto
0
1
CF19
Polarità PB4
0= Attivo contatto chiuso
1= Attivo contatto aperto
0
1
CF20
Configurazione RL4
0 = relè allarme
1 = parzializzazione compressore n° 1
2 = compressore n° 2
3 = ON/OFF ventilazione
4 = valvola di inversione
5 = resistenza antigelo / appoggio n°1
6 = solenoide lato acqua
7 = solenoide lato acqua solo in pompa di calore
8= resistenza antigelo / appoggio n° 2
9 = pompa acqua evaporatore / ventilatore di mandata
(macchine aria / aria)
10= pompa acqua condensatore
0
10
CF21
Configurazione RL5
0 = relè allarme
1 = parzializzazione compressore n° 1
2 = compressore n° 2
3 = ON/OFF ventilazione
4 = valvola di inversione
5 = resistenza antigelo / appoggio n°1
6 = solenoide lato acqua
7 = solenoide lato acqua solo in pompa di calore
8= resistenza antigelo / appoggio n° 2
9 = pompa acqua evaporatore / ventilatore di mandata
(macchine aria / aria)
10= pompa acqua condensatore
0
10
CF22
Valore di pressione a 4mA / 0,5V
0.0
0
50.0
725
Bar
Psi
Dec
int
CF23
Valore di pressione a 20mA / 5V
0.0
0
50.0
725
Bar
Psi
Dec
int
CF24
Offset PB1
-12.0
-21
12.0
21
°C
°F
Dec
int
CF25
Offset PB2
-12.0
-21
12.0
21
°C
°F
Dec
int
CF26
Offset PB3
-12.0
-21
-12.0
-174
12.0
21
12.0
174
°C
°F
Bar
Psi
Dec
int
dec
int
CF10
Configurazione ID5
0 = Compressor thermal 1
1 = Condensation fan thermal
2 = Evaporator flow switch
3 = Remote on / off
4 = remote chiller / heat pump
5 = Compressor thermal 2
6 = 2 compressor / step request
7 = End defrost
8 = Energy saving
9 = Antifreeze alarm
10 = Compressor 1 and 2 thermic
11 = Generic alarm signaling / blocking
12 = Evaporator / thermal water pump thermal alarm
supply fan
13 = Condenser water pump thermal alarm
14 = Condenser flow switch
15 = Disabled
0
15
CF11
CONFIGURATION
PB4
selected as a digital entry
0 = Compressor thermal 1
1 = Condensation fan thermal
2 = Evaporator flow switch
3 = Remote on / off
4 = remote chiller / heat pump
5 = Compressor thermal 2
6 = 2 compressor / step request
7 = End defrost
8 = Energy saving
9 = Antifreeze alarm
10 = Compressor 1 and 2 thermic
11 = Generic alarm signaling / blocking
12 = Evaporator / thermal water pump thermal alarm
supply fan
13 = Condenser water pump thermal alarm
14 = Condenser flow switch
15 = Disabled
0
15
CF12
Polarit
y
ID1
0= A
ctive close contact
1=
Active open contact
0
1
CF13
Polarit
y
ID2
0=
Active close contact
1=
Active open contact
0
1
CF14
Polarit
y
ID3
0=
Active close contact
1=
Active open contact
0
1
CF15
Polarit
y
ID4
0=
Active close contact
1=
Active open contact
0
1
CF16
Polarit
y
ID5
0=
Active close contact
1=
Active open contact
0
1
CF08
Configurazione ID1
0= Termica compressore 1
1= Termica ventilatore di condensazione
2= Flussostato evaporatore
3= On/off remoto
4= chiller / pompa di calore remoto
5= Termica compressore 2
6= Richiesta 2 compressore / gradino
7= Fine sbrinamento
8= Energy saving
9= Allarme antigelo
10= Termica compressori 1 e 2
11= Allarme generico segnalazione / blocco
12 = Allarme termica pompa acqua evaporatore / termica
ventilatore di mandata
13= Allarme termica pompa acqua condensatore
14= Flussostato condensatore
0
15
CF09
CONFIGURATION
ID2
0 = Compressor thermal 1
1 = Condensation fan thermal
2 = Evaporator flow switch
3 = Remote on / off
4 = remote chiller / heat pump
5 = Compressor thermal 2
6 = 2 compressor / step request
7 = End defrost
8 = Energy saving
9 = Antifreeze alarm
10 = Compressor 1 and 2 thermic
11 = Generic alarm signaling / blocking
12 = Evaporator / thermal water pump thermal alarm
supply fan
13 = Condenser water pump thermal alarm
14 = Condenser flow switch
15 = Disabled
0
15
CF27
Offset PB4
-12.0
-21
12.0
21
°C
°F
Dec
int
CF28
Chiller / heat pump selection
0=
Chiller and pump with keyboard selection
1=
Chiller and pump from digital input
2=
Chiller and pump
3=
Only
chiller
4=
Heat pump only
0
4
CF29
Set Change Over Automatic
-50.0
-58
110
230
°C
°F
Dec
int
CF30
Operating mode selection differential
0.1
0
25.0
45
°C
°F
Dec
int
CF31
Working logic
0=
chiller /
pdc
1=
chiller /
pdc
0
1
CF32
Selection
°C o °F
0= °C / °BAR
1= °F / °psi
0
1
CF33
Network frequency selection
0= 50 Hz
1= 60 Hz
2 =
The PWM output can drive an external alarm relay
0
2
CF34
I
Serial address
1
247
CF35
remote terminal
0=
Not used
1=
Model without probe on board
2=
Model with NTC probe on board
0
2
CF36
Display upper display
0 = PB1
1 = PB2
2 =
Anything
3 = PB4
4 = Setpoint
Real unity
5 =
Unit status
6 =
Anything
7 =
Anything
8 =
Job differential
9=
Unit setpoint (fixed value of the parameter)
0
9
CF37
Release firmware
CF38
Parameters map
EEprom
CF39
Configurazione RL2
0 = Alarm relay
1 = Compressor capacity control 1
2 = Compressor No. 2
3 = ON/OFF ventilation
4 = Reversing valve
5 = Antifreeze / support resistance n ° 1
6 = Water side solenoid
7 = Water side solenoid only in heat pump
8= Antifreeze / support resistance n ° 2
9 = Evaporator water pump / supply fan
(air / air machines)
10= Condenser water pump
0
10
CF40
Configurazione RL3
0 = Alarm relay
1 = Compressor capacity control 1
2 = Compressor No. 2
3 = ON/OFF ventilation
4 = Reversing valve
5 = Antifreeze / support resistance n ° 1
6 = Water side solenoid
7 = Water side solenoid only in heat pump
8= Antifreeze / support resistance n ° 2
9 = Evaporator water pump / supply fan
(air / air machines)
10= Condenser water pump
0
10
CF41
Configurazione uscita open collector
0 = Alarm relay
1 = Compressor capacity control 1
2 = Compressor No. 2
3 = ON/OFF ventilation
4 = Reversing valve
5 = Antifreeze / support resistance n ° 1
6 = Water side solenoid
7 = Water side solenoid only in heat pump
8= Antifreeze / support resistance n ° 2
9 = Evaporator water pump / supply fan
(air / air machines)
10= Condenser water pump
0
10
CF42
Valve reversal time on compressor standstill
0
250
Sec
CF43
Display upper display
0 = PB1
1 = PB2
2 = PB3
3 = PB4
4 = Setpoint
Real unity
5 =
Unit status
6 =
Timer
7 =
Anything
8 =
Job differential
9=
Unit setpoint (fixed value of the parameter)
0
9