- 141 -
UMC22-FBP
FieldBusPlug / Issue: 02.2008
V 6
Universal Motor Controller UMC22-FBP
Software version 4.0
Par.
No.
Menu
No.
Menu point name
Display:
7-segm.
Default
Range
Description / remark
take over
-
1.3.3
Communication
fault
UMC22 does not receive valid
telegramms: control system, fi eldbus
or FieldBusPlug is out of order or
interrupted or FieldBusPlug and
UMC22 slave address are different.
When the communication is correct
again after fault the motor can be star-
ted immediately without fault acknow-
ledge (3.3.1).
Remark:
Once the communication fault is
acknowledged the menu goes back
to "Show address" or to "Direct panel
control" resp. even there is still a com-
munication fault.
Procedure:
Fault [ENTER] F00x [ENTER] Acno
[ENTER] F - - - [MENU] Fault [MENU]
-
1.3.4
Parameter out of
range
Received parameter exeeds high or
low limit.
1.3.5
Current check-
back fault
No motor current within 300 ms after
switching on or motor current is still
fl owing 300 ms after switching off.
Assumption:
Check-back =
Motor current
1.3.6
OLS 0
1 without
close command
(Actuator)
Actuator only!
Open limit signal appears without
open command
1.3.7
Relay 1 check-
back fault
No 1-signal from auxiliary contact at
input DI1 within 300 ms after switching
on the contactor or 1-signal at input
DI1 even if contactor is not switched
on.
Assumption:
Check-back =
Auxiliary contacts
CLS 0
1 without
close open
(Actuator)
Actuator only!
Closed limit signal appears without
close command
Chapter 8.2.1~2