UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
Parameter
name /
Parameter
number
Remark
Parameter value
Description of parameter values
Contr
ol
system
(digital
value if
dif
fer
ent)
Contr
ol
Panel
Local control
22
(continued)
Off
(0)
Lc.cF
Off
: no local operation
(= default)
- Local operation via DIs: DI3*, DI4 and DI5 not used, free available
- Direct panel control: not active
On
(1)
Lc.co
On
- Local operation via DIs only (1):
- Local operation via DIs: DI3* and DI4 active signal, pulse
and DI5 closed circuit signal, pulse
- Direct panel control: not active
002
(2)
L.002
002
- Local operation via DIs only (2):
- Local operation via DIs: DI3*, DI4 and DI5 active signal, pulse
- Direct panel control: not active
003
(3)
L.003
003
- Local operation via DIs (1) and Direct panel control:
- Local operation via DIs: DI3* and DI4 active signal, pulse
and DI5 closed circuit signal, pulse
- Direct panel control: actived
004
(4)
L.004
004
- Local operation via DIs (2) and Direct panel control:
- Local operation via DIs: DI3*, DI4 and DI5 active signal, pulse
- Direct panel control: actived
005
(5)
L.005
005
- Direct panel control only:
- Local operation via DIs: DI3*, DI4 and DI5 not used, free available
- Direct panel control: actived
* DI3 is only used for the control functions
Reversing starter
,
Pole-changing starter
and
Actuator 1-4
.
006
(6)
L.006
006
- Local operation via DI3 und DI4: 1 signal as long as button pressed.
- DI5: closed circuit, pulse
- Direct control via Control Panel
007
(7)
L.007
007
- Local operation via DI3 und DI4: 1 signal as long as button pressed.
- DI5: true, pulse
- Direct control via Control Panel
008
(8)
L.008
008
- Local operation via DI3 und DI4: 1 signal as long as button pressed.
- DI5: closed circuit, pulse
009
(9)
L.009
009
- Local operation via DI3 und DI4: 1 signal as long as button pressed
- DI5: true, pulse
Low current
threshold
08
Accessible via control system only!
5-100 %
(1-20)
-
5-100 % x Set current
(step: 5 %): 5 % = 5 % x1
Warning when motor current is below threshold and start-up time has
elapsed.
Default vaule: 10 (= 50 %)
Multi-function
input
05 / 07 / 21
see DI0, DI1, DI2 Multi-function input
Chapter 4.3.4~12