![ABB UMC22-FBP Technical Description Download Page 159](http://html.mh-extra.com/html/abb/umc22-fbp/umc22-fbp_technical-description_3222159.webp)
- 159 -
UMC22-FBP
FieldBusPlug / Issue: 02.2008
V 6
Universal Motor Controller UMC22-FBP
Software version 4.0
Chapter 8.2.3~10
Par.
No.
Menu
No.
Menu point name
Display:
7-segm.
Default
Range
Description / remark
take over
21
(cont.)
3.7.60
-
3.7.69
Earth fault
monitoring
trip and warning
during
motor off
Menü No.
Display
Delay time
Menü No.
Display
Delay time
3.7.60
1 s
3.7.64
16 s
3.7.61
2 s
3.7.65-
3.7.69
-
25 s
3.7.62
4 s
3.7.63
8 s
3.7.70
-
3.7.79
Earth fault
monitoring
warning with
start-up inhibit
Menü No.
Display
Delay time
Menü No.
Display
Delay time
3.7.70
1 s
3.7.74
16 s
3.7.71
2 s
3.7.75-
3.7.79
-
25 s
3.7.72
4 s
3.7.73
8 s
3.7.80
-
3.7.89
Earth fault
monitoring
trip and warning
with start-up
inhibit
Menü No.
Display
Delay time
Menü No.
Display
Delay time
3.7.80
1 s
3.7.84
16 s
3.7.81
2 s
3.7.85-
3.7.89
-
25 s
3.7.82
4 s
3.7.83
8 s
24
3.8
Fault output
(4.3.4)
UMC22 output D02 can be used for
fault indication.
during
motor off
3.8.0
off
off
Fault output is not activated. DO2 free
available.
3.8.1
on
Fault output is activated. DO2 used for
fault indication (lights steady)
3.8.2
fl ashing
Fault output is activated. DO2 used for
fault indication (fl ashing)