- 50 -
UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
4.3.3 Transfer of the complete parameter set in one block (continued)
Wrd
No.
Byt
No.
Parameter name
Byte
weight
Defi nition / Range
Default value
Default
(digital)
take-over
after
1)
12
24
Star-delta starting
time
high
1-3600 s,
step: 0.1 s
60 s
600
motor off
25
low
13
26
Reverse lock-out time
high
0.2-3600 s,
step: 0.1 s
2 s
20
motor off
27
low
14
28
reserved
-
-
-
29
reserved
-
-
-
15
30
reserved
-
-
-
31
Emergency by PLC
Off (0),
On (1)
Off
0
motor off
16
32
reserved
-
-
-
-
33
reserved
-
-
-
-
17
34
reserved
-
-
-
-
35
reserved
-
-
-
-
18
36
Address check
Off (0),
On (1)
Off
0
power
up
37
Bus fault reaction
Relays off (0),
Outputs retain status (1)
Relays off
0
motor off
19
38
DI2 Multi-function
input
000 to 089
Transparent
000
motor off
39
Local control
Off (0), On (1), 002 (2), 003 (3),
004 (4), 005 (5), 006 (6) , 007 (7) ,
008 (8) , 009 (9)
Off
0
motor off
20
40
Blocking current
threshold
0-800 % * Set, current,
step: 5 %
800 %
160
motor off
41
Fault output
Off (0), On (1),
blink (3)
Off
0
motor off
1)
: but only when the internal fault bit is not set.
Chapter 4.3.3~2