- 68 -
UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
Parameter
name /
Parameter
number
Remark
Parameter value
Description of parameter values
Contr
ol
system
(digital
value if
dif
fer
ent)
Contr
ol
Panel
Start-up time
14
Accessible via control system only!
Suppresses Blocking / High current threshold / Low current threshold signals until motor is in nor-
mal running status.
0-600 s
(0-6000)
-
0-600 s
(step: 0.1 s): 600 s = 0.1 s x 6000
Default value: 1200 (=120 s)
Trip class
04
Accessible via control system or Control Panel (menu point: triP)!
Overload calculation (thermal memory)
Class 5
tr05
Trip class 5
Class 10
tr10
Trip class 10 (= default)
Class 20
tr20
Trip class 20
Class 30
tr30
Trip class 30