- 151 -
UMC22-FBP
FieldBusPlug / Issue: 02.2008
V 6
Universal Motor Controller UMC22-FBP
Software version 4.0
Chapter 8.2.3~2
Par.
No.
Menu
No.
Menu point name
Display:
7-segm.
Default
Range
Description / remark
take over
02
3.3
Current factor
(4.3.4)
The UMC22-FBP measures the cur-
rents of the lines in the bushing holes.
冑
3 wiring and/or the use of an external
current transformer result in a higher
power line current. To show e.g. the
real rated motor current the Current
factor has to be changed before or
together with the Set current.
Depending on the Current factor the
number of stages before the decimal
point fi ts to the desired range (More
details see menu point Current factor
and chapter 3.2.3 and 3.2.4).
With [Enter]:
during
motor off
3.3.1
show / change
1.0
1.0
1.7
10-640
- Current range: 0.24-63.00 A (de-
fault) 2 stages before decimal point
- Current range: 0.42-109.0 A
(1.7 is internally corrected into 1.73,
used for
冑
3 circuitry, up to 109.0 A
without external transformer)
3 stages before decimal point
- Current range: 10-3200 A
(supposed an external current
transformers with a secondary
current of 5 A).
3 stages before decimal point.
|
2 ... 5
Cable, looped through 2 ... 5 times