ISWGAPC3 is used to configure which protection function enables the current
multiplier if the INRPHAR1 function detects inrush. ISWGAPC4 is used to configure
the cooperation between the autoreclose function and the protection functions. The
autoreclose function DARREC1 can block protection functions according to the
application. SELGAPC2 is used to configure TCS blocking from the circuit breaker
open or close position. OSWGAPC17 is used for connecting switch onto fault
function CBPSOF. The inputs are start signals routed from the protection functions.
ISWGAPC3
PHLPTOC1_ENA_MULT
PHHPTOC1_ENA_MULT
PHHPTOC2_ENA_MULT
PHIPTOC1_ENA_MULT
EFHPTOC1_ENA_MULT
DEFLPDEF1_ENA_MULT
DEFLPDEF2_ENA_MULT
DEFHPDEF1_ENA_MULT
NSPTO C1_ENA_MULT
NSPTO C2_ENA_MULT
T1PTTR1_ENA_MULT
ISWGAPC4
PHLPTOC1_BLOCK
PHHPTOC1_BLOCK
PHHPTOC2_BLOCK
EFHPTOC1_BLOCK
DEFLPDEF1_BLOCK
DEFLPDEF2_BLOCK
DEFHPDEF1_BLOCK
SELGAPC2
TCSSCBR1_BLOCK
TCSSCBR2_BLOCK
SELGAPC1_OUT_2
SELGAPC1_OUT_3
CB Closed Position
CB Open Posit ion
PHLPTOC1_START
PHHPTOC1_START
PHHPTOC2_START
PHIPTOC1_START
EFHPTOC1_START
DEFLPDEF1_START
DEFLPDEF2_START
DEFHPDEF1_START
ROVPTOV1_START
ROVPTOV2_START
ROVPTOV3_START
INTRPTEF1_START
NSPTOC1_START
NSPTO C2_START
PDNSPTO C1_START
T1PTTR1_START
OSWGAPC17
St art
DLYD
CBPSOF1_INIT
GUID-A717CE52-5F4C-40C4-BF71-FBFCB900179B V2 EN
Figure 33:
Internal signal
ISWGAPC3
ISWGAPC3 input is used to configure which protection function enables current
multiplier while inrush is detected by INRPHAR1, by changing the ISWGAPC3
parameters. ISWGAPC3 input is routed from INRPHAR1 output
BLK2H
.
ISWGAPC3 outputs are connected to the
ENA_MULT
inputs of the protection
functions.
1MRS757456 D
Section 3
REF611 standardized configurations
REF611
55
Application Manual