autoreclose function DARREC1 can block protection functions according to the
application. SELGAPC2 is used to configure TCS blocking from the circuit breaker
open or close position. OSWGAPC17 is used for connecting switch onto fault
function CBPSOF. The inputs are start signals routed from the protection functions.
ISWGAPC3
DPHLPDOC1_ENA_MULT
DPHLPDOC2_ENA_MULT
DPHHPDOC1_ENA_MULT
PHIPTOC1_ENA_MULT
EFHPTOC1_ENA_MULT
DEFLPDEF1_ENA_MULT
DEFLPDEF2_ENA_MULT
DEFHPDEF1_ENA_MULT
NSPTOC1_ENA_MULT
NSPTOC2_ENA_MULT
T1PTTR1_ENA_MULT
ISWGAPC4
DPHLPDOC1_BLOCK
DPHLPDOC2_BLOCK
DPHHPDOC1_BLOCK
EFHPTOC1_BLOCK
DEFLPDEF1_BLOCK
DEFLPDEF2_BLOCK
DEFHPDEF1_BLOCK
SELGAPC2
TCSSCBR1_BLOCK
TCSSCBR2_BLOCK
INRPHAR1_BLK2H
DARREC1_PROT_CRD
SELGAPC1_OUT_2
SELGAPC1_OUT_3
CB Closed Position
CB Open Position
DPHLPDOC1_START
DPHLPDOC2_START
DPHHPDOC1_START
PHIPTOC1_START
EFHPTOC1_START
DEFLPDEF1_START
DEFLPDEF2_START
DEFHPDEF1_START
ROVPTOV1_START
ROVPTOV2_START
ROVPTOV3_START
INTRPTEF1_START
NSPTOC1_START
NSPTOC2_START
PTNSPTOC1_SRART
T1PTTR1_START
OSWGAPC17
CBPSOF1_INIT
Start
DLYD
GUID-895B4A93-7066-45C6-9EB1-680320A07FC6 V2 EN
Figure 123:
Internal signal
ISWGAPC3
ISWGAPC3 input is used to configure which protection function enables current
multiplier while inrush is detected by INRPHAR1 by changing the ISWGAPC3
parameters. ISWGAPC3 input is routed from INRPHAR1 output
BLK2H
.
ISWGAPC3 outputs are connected to
ENA_MULT
of the protection functions.
Section 3
1MRS757456 D
REF611 standardized configurations
142
REF611
Application Manual