trip and alarm signals are connected to SELGAPC3 via TPGAPC. TPGAPC are
timers and used for setting the minimum pulse length for the outputs.
SELGAPC3 outputs are connected to X100 binary outputs. If X130 optional card is
taken into use, SELGAPC3 outputs also connected to the X130 binary outputs.
SELGAPC3
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
OUT_9
IN_14
IN_15
IN_16
IN_17
IN_18
X100 PO1
X100 PO2
X100 SO1
X100 SO2
X100 PO3
X100 PO4
X130 SO1
X130 SO2
X130 SO3
1
)
1
)
Optional binary outputs
OSWGAPC11_OUT
OSWGAPC12_OUT
OSWGAPC13_OUT
OSWGAPC14_OUT
OSWGAPC15_OUT
OSWGAPC16_OUT
OSWGAPC5_OUT
OSWGAPC6_OUT
OSWGAPC7_OUT
OSWGAPC8_OUT
OSWGAPC9_OUT
OSWGAPC10_OUT
OSWGAPC3_OUT
OSWGAPC4_OUT
Start 1
Start 2
Start 3
Start 4
Trip 1
Alarm 1
Trip 2
Trip 3
Trip 4
Alarm 2
Alarm 3
Alarm 4
Alarm 5
Alarm 6
Backup Trip
CBXCBR_EXE_OP
DARREC_OPEN_CB
TRPPTRC1_TRIP
TRPPTRC2_TRIP
CBXCBR_EXE_CL
DARREC_CLOSE_CB
CCBRBRF1_TRBU
CB Open 1
CB Close
CB Open 2
TPGAPC1
IN1
OUT1
IN2
OUT2
TPGAPC7
IN1
OUT1
IN2
OUT2
TPGAPC6
IN1
OUT1
IN2
OUT2
TPGAPC5
IN1
OUT1
IN2
OUT2
TPGAPC4
IN1
OUT1
IN2
OUT2
TPGAPC3
IN1
OUT1
IN2
OUT2
TPGAPC2
IN1
OUT1
IN2
OUT2
GUID-3772666B-6FE9-48E5-91BF-9AA80BFD4B6E V1 EN
Figure 40:
SELGAPC3
SELGAPC4
SELGAPC4 is used to configure the OSWGAPC outputs to LEDs. Master trip signals
are connected to SELGAPC4 via TRPPTRC. Start, trip and alarm signals are
connected to SELGAPC4 directly. SELGAPC4 outputs are connected to
programmable LED1 to LED8.
1MRS757456 D
Section 3
REF611 standardized configurations
REF611
61
Application Manual