X100 SO1
X100 SO2
COMMON ALARM INDICATION 1 & 2
PHLPTOC1_OPERATE
PHHPTOC1_OPERATE
PHHPTOC2_OPERATE
PHIPTOC1_OPERATE
DEFLPDEF1_OPERATE
DEFLPDEF2_OPERATE
DEFHPDEF1_OPERATE
ROVPTOV1_OPERTAE
NSPTOC1_OPERATE
NSPTOC2_OPERATE
PDNSPTOC1_OPERATE
ROVPTOV2_OPERTAE
ROVPTOV3_OPERTAE
EFHPTOC1_OPETATE
INTRPTEF1_OPERATE
PHLPTOC1_START
PHHPTOC1_START
PHHPTOC2_START
PHIPTOC1_START
DEFLPDEF1_START
DEFLPDEF2_START
DEFHPDEF1_START
ROVPTOV1_START
NSPTOC1_START
NSPTOC2_START
PDNSPTOC1_START
ROVPTOV2_START
ROVPTOV3_START
EFHPTOC1_START
INTRPTEF1_START
OSWGAPC3
OR
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
OUT
IN_12
IN_13
IN_15
IN_14
OSWGAPC7
OR
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
OUT
IN_12
IN_13
IN_15
IN_14
SELGAPC3
OUT_3
IN_5
OUT_4
IN_9
TPGAPC1
IN1
OUT1
TPGAPC3
IN1
OUT1
GUID-9AFB34C6-4203-47D4-B03D-F071504B50D3 V1 EN
Figure 26:
Common alarm indication
The signal outputs from the protection relay are connected to give dedicated
information.
•
Start of any protection function SO1 (X100:10-12)
•
Operation (trip) of any protection function SO2 (X100: 13-15)
TPGAPC are timers and they are used for setting the minimum pulse length for the
outputs. There are seven generic timers (TPGAPC1…7) available in the protection
relay.
1MRS757456 D
Section 3
REF611 standardized configurations
REF611
49
Application Manual