SELGAPC1
Blocking 1
CCBRBRF1_PO SCLOSE
CBXCBR1_POSCLOSE
SELGAPC2_IN_1
CB Closed Position
CB O pen Position
DARREC1_CB_PO S
CBXCBR1_PO SOPEN
SELGAPC2_IN_2
Basic Angle Control
CBXCBR1_ENA_CLOSE
CB Close Enable
DARREC1_CB_READY
External Trip
PROTECTION_BI_SG_2
Setting Group 2
Blocking 2
PROTECTION_BI_SG_3
Setting Group 3
PROTECTIO N_BI_SG_4
Setting Group 4
ISWGAPC1_IN
ISWGAPC2_IN
X120/1-2 BI1
X120/3-2 BI2
X120/4-2 BI3
X120/5-6 BI4
X130/1-2 BI1
X130/3-2 BI2
X130/4-5 BI3
X130/6-5 BI4
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
TRPTTRC1_OPERATE
TRPTTRC2_OPERATE
X120-BI1
X120-BI2
X120-BI3
X120-BI4
X130-BI1
X130-BI2
X130-BI3
X130-BI4
Always True
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
OUT_9
OUT_10
OUT_11
OUT_12
OUT_13
ISWGAPC5_IN
DARREC1_RECL_ON
TRPTTRC1_RST_LKOUT
TRPTTRC2_RST_LKOUT
TRPTTRC1/2_
RST_LKOUT
GUID-E54640C9-1F74-420E-9486-E88430C753DA V1 EN
Figure 119:
SELGAPC1
ISWGAPC1
ISWGAPC1 is used to select which protection functions are to be blocked by changing
ISWGAPC1 parameters. ISWGAPC1 input is routed from SELGAPC1 output
OUT_1 Blocking 1
. ISWGAPC1 outputs are connected to the
BLOCK
inputs of
the protection functions.
1MRS757456 D
Section 3
REF611 standardized configurations
REF611
139
Application Manual