ISWGAPC3
IN
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
OUT_9
OUT_10
OUT_11
INRPHAR1_BLK2H
PHLPTOC1_ENA_MULT
PHHPTOC1_ENA_MULT
PHHPTOC2_ENA_MULT
PHIPTOC1_ENA_MULT
EFHPTOC1_ENA_MULT
DEFLPDEF1_ENA_MULT
DEFLPDEF2_ENA_MULT
DEFHPDEF1_ENA_MULT
NSPTOC1_ENA_MULT
NSPTOC2_ENA_MULT
T1PTTR1_ENA_MULT
GUID-CC7AF316-6030-4959-B6EE-032E6415804C V1 EN
Figure 34:
ISWGAPC3
ISWGAPC4
ISWGAPC4 input is used to configure which protection function is blocked by the
autoreclosing function by changing the ISWGAPC4 parameters. ISWGAPC4 input is
routed from DARREC1 output
PROT_CRD
. ISWGAPC4 outputs are connected to the
BLOCK
inputs of some of the protection functions.
ISWGAPC4
IN
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
DARREC1_PROT_CRD
PHLPTOC1_BLOCK
PHHPTOC1_BLOCK
PHHPTOC2_BLOCK
EFHPTOC1_BLOCK
DEFLPDEF1_BLOCK
DEFLPDEF2_BLOCK
DEFHPDEF1_BLOCK
GUID-E0106013-2B27-4DED-81C7-40ED4F0A94F0 V1 EN
Figure 35:
ISWGAPC4
SELGAPC2
SELGAPC2 inputs represent the circuit breaker closed and open position from
SELGACP1. SELGAPC2 outputs are routed to the
BLOCK
input of the trip circuit
supervision TCSSCBR1 and TCSSCBR2.
By default, X100 PO3 and PO4 are both used for the open circuit breaker. TCSSCBR1
and TCSSCBR2 are both blocked by the circuit breaker open position. If X100-PO3
is used for closing the circuit breaker, TCSSCBR1 needs to be blocked by circuit
breaker close position (OUT_1 connection=IN_1). If X100-PO4 is used for closing
Section 3
1MRS757456 D
REF611 standardized configurations
56
REF611
Application Manual