3.5.3.3
Functional diagrams for control
OR
X100 PO3
TRIP
CL_LKOUT
BLOCK
RST_LKOUT
TRPPTRC1
OPERATE
X100 PO4
MASTER TRIP #1
MASTER TRIP #2
OR
OR
TRIP
CL_LKOUT
BLOCK
RST_LKOUT
TRPPTRC2
OPERATE
SELGAPC3
OUT_6
IN_2
SELGAPC3
OUT_5
IN_1
SELGAPC1
OUT_4
IN_4
SELGAPC1
OUT_4
IN_4
OSWGAPC2
OR
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
OUT
IN_12
X120-BI4
PHLPTOC1_OPERATE
PHHPTOC1_OPERATE
PHHPTOC2_OPERATE
PHIPTOC1_OPERATE
EFLPTOC2_OPERATE
EFHPTOC1_OPERATE
EFIPOTC1_OPERATE
NSPTOC1_OPERATE
NSPTOC2_OPERATE
PDNSPTOC1_OPERATE
EFLPTOC1_OPETATE
CCBRBRF1_TRRET
OSWGAPC1
OR
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
OUT
DARREC1_OPEN_CB
CBXCBR1_EXE_OP
PHLPTOC1_OPERATE
PHHPTOC1_OPERATE
PHHPTOC2_OPERATE
PHIPTOC1_OPERATE
EFLPTOC2_OPERATE
EFHPTOC1_OPERATE
EFIPOTC1_OPERATE
NSPTOC1_OPERATE
NSPTOC2_OPERATE
PDNSPTOC1_OPERATE
EFLPTOC1_OPETATE
X120-BI4
RST_LKOUT
RST_LKOUT
SELGAPC1_External Trip
Q1
Q2
IN1
IN2
MVGAPC1
OR
GOOSERCV_BIN 2_OUT
GOOSERCV_BIN 3_OUT
SELGAPC1_External Trip
Q1
Q2
IN1
IN2
MVGAPC1
OR
GOOSERCV_BIN 2_OUT
GOOSERCV_BIN 3_OUT
GUID-66E79F27-D704-4BD5-8778-5B1BB863D7D8 V4 EN
Figure 69:
Master trip
The operate signals from the protections and an external trip are connected to the two
trip output contacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding
Master Trips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit
breaker from local or remote CBXCBR1_EXE_OP or from the autoreclosing
DARREC1_OPEN_CB are connected directly to the output contact PO3
(X100:15-19).
1MRS757456 D
Section 3
REF611 standardized configurations
REF611
91
Application Manual