breaker close position (OUT_1 connection=IN_1). If X100-PO4 is used for closing
the circuit breaker, TCSSCBR2 needs to be blocked by the circuit breaker close
position (OUT_2 connection=IN_1).
SELGAPC2
IN_1
IN_2
OUT_1
OUT_2
TCSSCBR1_BLOCK
TCSSCBR2_BLOCK
SELGAPC1_OUT_2
SELGAPC1_OUT_3
CB Closed Position
CB Open Position
GUID-A7E79381-BE10-41E9-BCBC-AC27E8E64CBB V1 EN
Figure 126:
SELGAPC2
OSWGAPC17
OSWGAPC17 is used to route the protection function start signals to the
StartDLYD
input of the switch onto fault function CBPSOF. CBPSOF provides an
instantaneous trip or a time delayed trip when closing the breaker while a fault exists.
OSWGAPC17 output is connected to CBPSOF function indicating the detected fault.
OSWGAPC17
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
IN_14
IN_15
IN_16
EFHPTOC1_START
DEFLPDEF1_START
ROVPTOV2_START
ROVPTOV3_START
INTRPTEF1_START
DPHLPDOC1_START
NSPTOC1_START
PHIPTOC1_START
DEFLPDEF2_START
DEFHPDEF1_START
ROVPTOV1_START
DPHHPDOC1_START
DPHLPDOC2_START
NSPTOC2_START
PDNSPTOC1_START
T1PTTR1_START
Start DLYD
CBPSOF1_INIT
GUID-1C9AD42F-21FA-4539-93EE-CF0EFA4EB4B0 V2 EN
Figure 127:
OSWGAPC17
3.6.4.3
Binary outputs and LEDs
In configuration C, signals are routed to binary outputs and LEDs are configured by
OSWGAPC. The 16 OSWGAPC instances are categorized in four groups, including
Section 3
1MRS757456 D
REF611 standardized configurations
144
REF611
Application Manual