X120-BI3
OR
LED 7
TRIP CIRCUIT SUPERVISION
SELGAPC1
OUT_3
IN_3
TRPPTRC1_TRIP
TRPPTRC2_TRIP
TCSSCBR1
BLOCK
ALARM
TCSSCBR2
BLOCK
ALARM
SELGAPC4
OUT_7
IN_16
OSWGAPC14
OR
OUT
IN_3
IN_4
SELGAPC2
OUT_1
IN_2
OUT_2
CB Open Position
GUID-50B079D8-AE34-4D47-BD5F-ACCBBEC0EC18 V2 EN
Figure 23:
Trip circuit supervision
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked by
the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open position.
The TCS alarm indication is connected to LED 7.
Section 3
1MRS757456 D
REF611 standardized configurations
46
REF611
Application Manual
Summary of Contents for REF611
Page 1: ...Relion 611 series Feeder Protection and Control REF611 Application Manual ...
Page 2: ......
Page 10: ...4 ...
Page 174: ...168 ...
Page 184: ...178 ...
Page 187: ...181 ...