ISWGAPC3
IN
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
OUT_9
OUT_10
OUT_11
INRPHAR1_BLK2H
PHLPTOC1_ENA_MULT
PHHPTOC1_ENA_MULT
PHHPTOC2_ENA_MULT
PHIPTOC1_ENA_MULT
EFLPTOC1_ENA_MULT
EFLPTOC2_ENA_MULT
EFHPTOC1_ENA_MULT
EFIPTOC1_ENA_MULT
NSPTOC1_ENA_MULT
NSPTOC2_ENA_MULT
T1PTTR1_ENA_MULT
GUID-0FB9BAD2-E624-4310-A267-6E71E936A803 V1 EN
Figure 78:
ISWGAPC3
ISWGAPC4
ISWGAPC4 input is used to configure which protection function is blocked by the
autoreclosing function by changing the ISWGAPC4 parameters. ISWGAPC4 input is
routed from DARREC1 output
PROT_CRD
. ISWGAPC4 outputs are connected to the
BLOCK
inputs of some of the protection functions.
ISWGAPC4
IN
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
DARREC1_PROT_CRD
PHLPTOC1_BLOCK
PHHPTOC1_BLOCK
PHHPTOC2_BLOCK
EFLPTOC1_BLOCK
EFLPTOC2_BLOCK
EFHPTOC1_BLOCK
GUID-C935C34F-80CD-4A23-99BC-D997FC45B22F V1 EN
Figure 79:
ISWGAPC4
SELGAPC2
SELGAPC2 inputs are the circuit breaker closed and open positions routed from
SELGACP1. SELGAPC2 outputs are routed to the
BLOCK
input of the trip circuit
supervision functions TCSSCBR1 and TCSSCBR2.
By default, X100-PO3 and PO4 are both used for the open circuit breaker.
TCSSCBR1 and TCSSCBR2 are both blocked by the circuit breaker open position. If
X100-PO3 is used for closing the circuit breaker, TCSSCBR1 need to be blocked by
the circuit breaker close position (OUT_1 connection=IN_1). If X100-PO4 is used for
1MRS757456 D
Section 3
REF611 standardized configurations
REF611
99
Application Manual