LED 2
EARTH-FAULT PROTECTION
SELGAPC4
OUT_2
IN_11
OSWGAPC9
OR
OUT
IN_5
IN_6
IN_7
IN_8
EFLPTOC1
Io>(1)
51N-1(1)
BLOCK
START
OPERATE
Io
ENA_MULT
EFLPTOC2
Io>(2)
51N-1(2)
BLOCK
START
OPERATE
Io
ENA_MULT
EFIPTOC1
Io>>>(1)
50N(1)
BLOCK
START
OPERATE
Io
ENA_MULT
EFHPTOC1
Io>>(1)
51N-2(1)
BLOCK
START
OPERATE
Io
ENA_MULT
GUID-A3A385B1-89E2-4E71-9C18-183C9A1F9660 V1 EN
Figure 63:
Earth-fault protection
Four stages are offered for non-directional earth-fault protection.
All operate signals are connected to the Master Trip as well as to the alarm LED 2.
1MRS757456 D
Section 3
REF611 standardized configurations
REF611
85
Application Manual