OSWGAPC2
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
OUT
EFHPTOC1_OPERATE
DEFLPDEF1_OPERATE
ROVPTOV2_OPERATE
ROVPTOV3_OPERATE
INTRPTEF1_OPERATE
DPHLPDOC1_OPERATE
NSPTOC1_OPERATE
PHIPTOC1_OPERATE
DEFLPDEF2_OPERATE
DEFHPDEF1_OPERATE
ROVPTOV1_OPERATE
DPHHPDOC1_OPERATE
DPHLPDOC2_OPERATE
TRPPTRC2_OPERATE
IN_14
IN_15
IN_16
IN_17
NSPTOC2_OPERATE
PDNSPTOC1_OPERATE
T1PTTR1_OPERATE
CCBRBRF1_TRRET
Master trip 1
IN_18
CBPSOF1_OPERATE
GUID-DB9586F1-284E-449B-8D3F-BD6EFD237C81 V2 EN
Figure 133:
OSWGAPC2
Start OSWGAPCs
OSWGAPC instances 3...6 are used to configure the protection start signals. These
four OSWGAPCs have the same inputs from the protection function start signals. The
output is routed to SELGAPC3 via TPGAPC timer, and routed to SELGAPC4
directly.
1MRS757456 D
Section 3
REF611 standardized configurations
REF611
151
Application Manual