6.4.
Current transformers installation
Special care has to be taken for the connection and location of the CT’s: it is
the most current source of problems occurring at commissioning stage.
WARNING: when connecting the CT’s to the PQFA, the secondaries of
the CT’s have to be short-circuited.
First of all, the CT’s have to be positioned for closed loop control: they have to
monitor the resulting current after filtering.
The CT’s must also be positioned in the correct direction around the power
cable: the K (or P1) side should be in the direction of the supply and the L (or
P2) side should be in the direction of the load.
6.4.1. CT’s connection to the PQFA
The connections between the CT’s and the filter must satisfy the following
scheme:
? ?
The k terminal of line 1 CT is connected to terminal X5-1 of the filter
? ?
The l terminal of line 1 CT is connected to terminal X5-2 of the filter
? ?
The k terminal of line 2 CT is connected to terminal X5-3 of the filter
? ?
The l terminal of line 2 CT is connected to terminal X5-4 of the filter
? ?
The k terminal of line 3 CT is connected to terminal X5-5 of the filter
? ?
The l terminal of line 3 CT is connected to terminal X5-6 of the filter
Summary of Contents for PQFA
Page 1: ...Instructions Manual PQFA Power Quality Filter ABB Jumet ...
Page 19: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 19 Master cubicle view Zoom on next page ...
Page 20: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 20 ...
Page 21: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 21 Control rack details ...
Page 22: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 22 Master cubicle door view ...
Page 24: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 24 ...
Page 25: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 25 Slave cubicle door view ...
Page 28: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 28 ...