PQFA Instructions Manual
Asea Brown Boveri Jumet S.A.
8
Distorted networks may also cause generators malfunctions.
Overall it may be concluded that an excessive amount of harmonics leads to a
premature ageing of the electrical installation. This is an important motivation
for taking action against harmonics.
3.2.
General principle of active filtering
The active filter measures the harmonic currents and generates actively a
harmonic current spectrum in opposite phase to the measured distorting
harmonic current. The original harmonics are thereby cancelled. The principle
is shown in figure 3.2.
Figure 3.2. Principle of active filtering
The control of the active filter in combination with the active generation of the
compensating current allows for a concept that may not be overloaded.
Harmonic currents exceeding the capacity of the active filter will remain on the
network, but the filter will operate and eliminate all harmonic currents up to its
capacity.
The principle of active filter showing currents and spectra is clarified in Figure
3.3.
PQFA
Supply
Load
Fundamental only
- 1 . 3
1 . 3
0
360
- 1 . 3
1 . 3
0
3 6 0
- 1 . 3
1 . 3
0
360
i
distortion
i
compensation
Summary of Contents for PQFA
Page 1: ...Instructions Manual PQFA Power Quality Filter ABB Jumet ...
Page 19: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 19 Master cubicle view Zoom on next page ...
Page 20: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 20 ...
Page 21: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 21 Control rack details ...
Page 22: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 22 Master cubicle door view ...
Page 24: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 24 ...
Page 25: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 25 Slave cubicle door view ...
Page 28: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 28 ...