2. Upon reception
2.1.
Delivery inspection
Each PQFA is delivered in a sealed package designed to protect adequately
the equipment during shipment.
Upon receipt of the equipment, make sure that the packing is in good
condition.
After removal of the packing, check visually the exterior and interior of your
filter. Any loss or damage should be notified immediately.
Care should be taken to ensure that correct handling facilities are used.
2.2.
Identification tag
Each PQFA is fitted with a nameplate for identification purposes. The
nameplate includes the type of filter, nominal frequency, voltage and current
as well as a serial number and an ABB internal article code.
This information should always remain readable to ensure proper identification
during the whole life of the filter.
2.3.
Storage
PQFA packing is made for a storage period of maximum six months (transport
time included from delivery date EXW ABB Jumet factory). Packing for longer
storage period can be done on request.
If your PQFA is not installed once unpacked, it should be stored in a clean
indoor, dry, dust free and non-corrosive environment. The storage
temperature must be between –15°C and 70°C with a maximum relative
humidity of 95%, non-condensing.
Before installing and operating your PQFA, you should read very carefully this
instructions manual and you should make sure that the information given on
the nameplate corresponds to your network.
2.4.
Long storage period and reforming
If your PQFA is non-operational or stored for more than one year, the DC
capacitors need to be reformed (re-aged). Without reforming, capacitors may
be damaged when the filter starts to operate.
The reforming methods are described in chapter 12 (maintenance).
Summary of Contents for PQFA
Page 1: ...Instructions Manual PQFA Power Quality Filter ABB Jumet ...
Page 19: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 19 Master cubicle view Zoom on next page ...
Page 20: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 20 ...
Page 21: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 21 Control rack details ...
Page 22: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 22 Master cubicle door view ...
Page 24: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 24 ...
Page 25: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 25 Slave cubicle door view ...
Page 28: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 28 ...