- If the cable section found is bigger than the previously found value, step 2
and 3 have to be repeated until the cable sections are equal (see example
below).
Remark: during this process, it can be found that more than one cable per
phase is needed. The process has then to be applied on each cable as shown
in the example n°3 below.
S
S
e
e
c
c
t
t
i
i
o
o
n
n
50Hz
60Hz
[mm
2
]
Al
Cu
Al
Cu
16
1.01
1.01
1.01
1.01
25
1.01
1.02
1.01
1.03
35
1.02
1.03
1.02
1.04
50
1.03
1.06
1.04
1.08
70
1.05
1.1
1.06
1.13
95
1.08
1.16
1.10
1.21
120
1.11
1.30
1.15
1.30
150
1.16
1.30
1.21
1.39
185
1.22
1.41
1.28
1.50
240
1.31
1.55
1.40
1.66
300
1.41
1.70
1.52
1.84
Table: Multiplication factors for different cable types
Examples:
Please note that the following examples are given for information only
(see important remark above).
Example n°1:
PQF-L 80A 480V 60hz
Step 1: I
N
= 80A
?
cable section (*) = 25 [mm
2
]
Step 2: multiplication factor for a 25 [mm
2
] copper cable at 60hz = 1.03
Step 3: I = I
N
x 1.03 = 80A x 1.03 = 83 A
Step 4: I = 83A
?
cable section (*) : 25 [mm
2
]
This section is equal to the section found in the previous step.
Result : one copper cable of 25 [mm
2
] per phase
Summary of Contents for PQFA
Page 1: ...Instructions Manual PQFA Power Quality Filter ABB Jumet ...
Page 19: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 19 Master cubicle view Zoom on next page ...
Page 20: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 20 ...
Page 21: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 21 Control rack details ...
Page 22: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 22 Master cubicle door view ...
Page 24: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 24 ...
Page 25: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 25 Slave cubicle door view ...
Page 28: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 28 ...