PQFA Instructions Manual
Asea Brown Boveri Jumet S.A.
97
Step 6
Check ambient temperature and equipment ventilation
operation.
Step 7
Restart the PQFA according to commissioning procedure.
12.3. Fan
The cooling fan lifespan is about 5 years, depending on usage and ambient
temperature.
Fan failure is often preceeded by increasing noise from the bearings and rise
of the heatsink temperature despite cleaning. It is recommended to replace
the fan once these symptoms appear.
12.4. Capacitors reforming
If the filter has been non-operational for more than one year, DC capacitors
must be reformed (re-aged) before use. Without reforming, capacitors may be
damaged at start-up.
Stocked or non-operational filters should be reformed once a year. The
method indicated below assumes that the filter is stocked in a clean and dry
environment.
To reform the capacitors, switch the power on for about 2 hours, with all
harmonics and reactive power deselected.
If the filter has been left more than 2 years without operation, please contact
your ABB service provider.
Summary of Contents for PQFA
Page 1: ...Instructions Manual PQFA Power Quality Filter ABB Jumet ...
Page 19: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 19 Master cubicle view Zoom on next page ...
Page 20: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 20 ...
Page 21: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 21 Control rack details ...
Page 22: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 22 Master cubicle door view ...
Page 24: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 24 ...
Page 25: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 25 Slave cubicle door view ...
Page 28: ...PQFA Instructions Manual Asea Brown Boveri Jumet S A 28 ...